Product overview
AST6200 S11 is the 1000–1140 V three-phase class for project and panel engineers specifying motor soft starting at this supply voltage. Its catalog range is 15–800 kW and 10–560 A. S6 and S4 ratings must not be extended to S11.

A dedicated 1000–1140 V model schedule
Check the complete electrical assembly: supply and motor ratings, motor insulation and connection, isolation and protective devices, clearances, control supply and cabinet environment. The starter must be integrated into a suitable design for the actual installation. This page does not imply hazardous-area, mining or other application-specific certification.
The catalog lists AST6200-S11-200 at 200 kW / 150 A and AST6200-S11-800 at 800 kW / 560 A. Confirm the exact nameplate current, load torque, start duration and starts per hour. A matching voltage and kW label alone is insufficient for final approval.
S11 model selection table
1000–1140 V three-phase AC · 15–800 kW · 10–560 A
Source: AST6200 English Catalog V2612, S11 model selection. Power is a catalog reference. Confirm the selected model against motor rated current and duty; do not substitute another voltage-class table.
Functions and performance
| Function | What it provides |
|---|---|
| Starting modes | Voltage ramp, current-limit and torque starting |
| Starting adjustment | Starting time 1–120 s; initial voltage 30–80%; current-limit setting 50–600% |
| Stopping | Free/coast stop or soft stop; soft-stop time 0–60 s |
| Control | Local keypad, external terminals or communication control, with selectable combinations |
| Display | Removable Chinese/English LCD; operating status, current, voltage and fault information |
| Communication | RS485 Modbus RTU as standard |
| Feedback | One running relay, two programmable relay outputs and 4–20 mA analog output |
| Protection | Configurable overload, overcurrent, voltage, phase, unbalance, underload and thermal functions |
Adjustment ranges are parameter limits, not a guarantee that every motor can start at every setting. Starting duty, load torque and the motor thermal limits govern commissioning. Review the protection response settings: starting overcurrent and underload are set to Ignore by default in the V2612 manual.
Applications and selection workflow
- Pumps and water systems: confirm motor current, hydraulic starting conditions and the desired stopping behavior.
- Fans and blowers: provide inertia and required acceleration, especially for long run-up times.
- Conveyors and compressors: identify loaded or unloaded starting and the equipment interlocks.
- For every application, specify starts per hour, ambient temperature, altitude, enclosure and cooling.
Select the voltage class first, then current rating and duty. Confirm local or remote control, relay functions and PLC communication. Ask INOMAX to review the proposed model before fabrication or order.
Installation and operating conditions
| Item | AST6200 specification / selection requirement |
|---|---|
| Motor | Three-phase squirrel-cage asynchronous motor |
| Supply frequency | 30–70 Hz supply frequency; this is not a variable output-frequency range |
| Enclosure and cooling | IP20 unit, forced-air cooling, indoor installation |
| Ambient temperature | −10 to +40 °C; confirm suitability outside the specified range |
| Altitude | Below 2,000 m; derating is required above this altitude |
| Humidity and vibration | Below 95% RH, non-condensing; vibration below 0.5 G |
| Panel design | Keep cooling paths clear; exclude conductive dust, corrosive and explosive gases |
| Duty rating | Select by motor rated current, starting time, load and starts per hour |
Provide upstream isolation and protective devices to the installation design. Do not connect capacitors to the soft starter output. Electrical installation and commissioning must follow the manual and applicable site requirements.
Custom cabinet-type soft starter
INOMAX can supply AST6200 as a custom cabinet-type soft starter for project, system-integrator and OEM requirements. For S11 1000–1140 V projects, provide the complete system voltage and earthing requirements so the cabinet components and insulation arrangement can be reviewed.
Specify the required enclosure protection, installation environment, incoming isolation and protection, door controls, cable entry and cooling arrangement. Cabinet dimensions, component selection and supply scope are confirmed for the quoted configuration. The IP20 rating and dimensions in a standard AST6200 datasheet describe the starter unit, not the completed cabinet.

Download a datasheet by voltage and power
Choose the motor supply voltage first, then find its kW reference and compare the starter current with the motor nameplate. Download links show voltage and power as well as the AST6200 model, so the file can be selected without knowing the model code in advance.
- 220–240 V · 5.5–400 kW model datasheets
- 380–480 V · 7.5–800 kW model datasheets
- 520–690 V · 7.5–1400 kW model datasheets
- 1000–1140 V · 15–800 kW model datasheets
These PDFs describe individual starter units. For a custom cabinet, request the agreed cabinet specification and controlled dimensional drawing from info@inomaxtechnology.com.
Frequently asked questions
Is this a variable frequency drive?
No. AST6200 is a motor soft starter. Use a VFD when the process requires continuous speed regulation; 30–70 Hz is the specified supply-frequency range.
Does the power rating alone determine the model?
No. Compare the actual motor rated current, supply voltage, load, start time and starts per hour. Confirm any derating and the selected model data sheet.
Can it replace an existing starter without panel changes?
Replacement requires review of the existing wiring, protection, control signals, dimensions and thermal arrangement. A matching kW rating does not establish a direct replacement.
Catalog, manual and selection support
AST6200 English Catalog — V2612 (PDF) · AST6200 User Manual — V2612 (PDF)
Specifications on this page refer to these AST6200 editions. Use the supplied unit nameplate and applicable manual for final installation and commissioning. Download the selected model datasheet using the voltage and power links above. Ask INOMAX for the controlled dimensional drawing and agreed cabinet specification before fabrication.
Soft starter selection for pumps, fans and heavy loads · Browse all AST6200 product options
Specify your AST6200
Send the motor nameplate, application and starts per hour. INOMAX can review the voltage class, current rating, control requirements and cabinet arrangement before quotation.
Email: info@inomaxtechnology.com. Confirm warranty coverage, support scope, availability and delivery schedule for the quoted model and destination.