INOMAX SHF passive harmonic filters are installed at the input of six-pulse rectifiers to reduce current distortion and harmonic content and improve equipment power factor. Applications include VFDs, DC drives, UPS systems and centralized uncontrolled EV charging rectifiers.
Power, voltage and current range
| Configuration | Power reference kW | Rated current A | Models |
|---|---|---|---|
| 400 V / 50 Hz · SHF · 5% THDi design | 2.2–315 | 5–600 | 18 |
| 400 V / 50 Hz · SHF · 10% THDi design | 2.2–315 | 5–600 | 18 |
Choose the applicable configuration below. Voltage, current and power ranges vary by series and are not interchangeable across all models.
Application and connection

Choose the harmonic target
Separate SHF ranges are listed for current THD targets of ≤5% and ≤10%.
Improve equipment power factor
The technical specification lists power-factor improvement from 0.8 to 0.9 for the stated application.
Plan cabinet cooling
Model tables include heat loss and minimum cabinet airflow to support thermal design.
Plan the complete installation
Review branch current, branch-cable cross-section, mounting hardware, outline dimensions and weight alongside the main current rating.
Technical specifications
| Parameter | Specification |
|---|---|
| Rated voltage / frequency | 3-phase AC 400 V; 50 Hz |
| Insulation class | F |
| Noise level | ≤75 dB |
| Dielectric strength | AC 3000 V, 50 Hz, 5 s; leakage ≤5 mA; remove external capacitors for the phase-to-phase test |
| Power factor | Improved from 0.8 to 0.9 |
| Current THD | ≤5% or ≤10%, according to selected SHF range and operating conditions |
| Ambient temperature | −25°C to +40°C |
30 kW VFD harmonic-filter test
The following analyzer images show voltage/current waveforms and current harmonic measurements before and after installing a passive harmonic filter at the input of a 30 kW VFD.


Model selection and installation data
Specify rectifier input current, operating load range, supply voltage and frequency, and the required harmonic target. Verify performance for the intended network and operating conditions. Contact INOMAX for other voltage, frequency or THDi requirements.
36 model ratings shown
Expand a configuration to compare models. On a phone, swipe the table horizontally to see all dimensions.
400 V / 50 Hz · SHF · 5% THDi design · 18 models
| Model | Figure | Rated A | Drive kW | Branch A | Heat loss W | Min. airflow m³/min | Weight kg | W mm | D mm | H mm | W0 mm | H0 mm | Mounting screws | Branch cable mm² |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SHF-0005-5% | A | 5 | 2.2 | 2.5 | 176 | 0.9 | 19 | 270 | 250 | 480 | 180 | 453 | M10 | 1.5 |
| SHF-0010-5% | A | 10 | 3.7 | 5 | 207 | 1.1 | 24 | 270 | 250 | 480 | 180 | 453 | M10 | 1.5 |
| SHF-0016-5% | A | 16 | 7.5 | 8 | 323 | 1.7 | 29 | 270 | 250 | 480 | 180 | 453 | M10 | 2.5 |
| SHF-0025-5% | A | 25 | 11 | 12.5 | 386 | 2.0 | 35 | 270 | 250 | 480 | 180 | 453 | M10 | 4 |
| SHF-0030-5% | A | 30 | Confirm* | 15 | 453 | 2.4 | 46 | 300 | 220 | 680 | 210 | 653 | M10 | 4 |
| SHF-0045-5% | A | 45 | 22 | 22.5 | 581 | 3.0 | 56 | 300 | 220 | 680 | 210 | 653 | M10 | 6 |
| SHF-0060-5% | B | 60 | 30 | 28.7 | 602 | 3.1 | 90 | 363 | 280 | 740 | 280 | 713 | M10 | 6 |
| SHF-0075-5% | B | 75 | 37 | 35.8 | 773 | 4.0 | 98 | 363 | 280 | 740 | 280 | 713 | M10 | 10 |
| SHF-0090-5% | C | 90 | 45 | 43 | 909 | 4.7 | 125 | 455 | 375 | 950 | 350 | 920 | M12 | 10 |
| SHF-0110-5% | C | 110 | 55 | 52.5 | 1007 | 5.2 | 140 | 455 | 375 | 950 | 350 | 920 | M12 | 16 |
| SHF-0150-5% | C | 150 | 75 | 71.6 | 1061 | 5.5 | 170 | 455 | 375 | 950 | 350 | 920 | M12 | 25 |
| SHF-0180-5% | C | 180 | 90 | 86 | 1218 | 6.3 | 195 | 455 | 375 | 950 | 350 | 920 | M12 | 25 |
| SHF-0220-5% | C | 220 | 110 | 105 | 1398 | 7.2 | 215 | 485 | 415 | 1085 | 375 | 1055 | M12 | 35 |
| SHF-0260-5% | C | 260 | 132 | 124.1 | 1499 | 7.7 | 245 | 485 | 415 | 1085 | 375 | 1055 | M12 | 50 |
| SHF-0320-5% | C | 320 | 160 | 152.8 | 1577 | 8.1 | 300 | 485 | 415 | 1085 | 375 | 1055 | M12 | 70 |
| SHF-0400-5% | D | 400 | 200 | 190.9 | 1944 | 9.9 | 384 | 485 | 485 | 1230 | 375 | 1200 | M12 | 95 |
| SHF-0480-5% | D | 480 | 250 | 229.2 | 2291 | 10.5 | 417 | 525 | 485 | 1400 | 415 | 1370 | M12 | 95 |
| SHF-0600-5% | Cabinet | 600 | 315 | 286.5 | 2776 | 12.8 | 500 | 800 | 800 | 2000 | / | / | — | / |
400 V / 50 Hz · SHF · 10% THDi design · 18 models
| Model | Figure | Rated A | Drive kW | Branch A | Heat loss W | Min. airflow m³/min | Weight kg | W mm | D mm | H mm | W0 mm | H0 mm | Mounting screws | Branch cable mm² |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SHF-0005-10% | A | 5 | 2.2 | 2.5 | 168 | 0.9 | 19 | 270 | 250 | 480 | 180 | 453 | M10 | 1.5 |
| SHF-0010-10% | A | 10 | 3.7 | 5 | 196 | 1.1 | 24 | 270 | 250 | 480 | 180 | 453 | M10 | 1.5 |
| SHF-0013-10% | A | 13 | 7.5 | 8 | 318 | 1.7 | 29 | 270 | 250 | 480 | 180 | 453 | M10 | 2.5 |
| SHF-0025-10% | A | 25 | 11 | 12.5 | 378 | 2.0 | 35 | 270 | 250 | 480 | 180 | 453 | M10 | 4 |
| SHF-0030-10% | A | 30 | 15 | 15 | 445 | 2.4 | 46 | 300 | 220 | 680 | 210 | 653 | M10 | 4 |
| SHF-0045-10% | A | 45 | 22 | 22.5 | 572 | 3.0 | 56 | 300 | 220 | 680 | 210 | 653 | M10 | 6 |
| SHF-0060-10% | B | 60 | 30 | 28.7 | 593 | 3.1 | 90 | 363 | 280 | 740 | 280 | 713 | M10 | 6 |
| SHF-0075-10% | B | 75 | 37 | 35.8 | 765 | 4.0 | 98 | 363 | 280 | 740 | 280 | 713 | M10 | 10 |
| SHF-0090-10% | C | 90 | 45 | 43 | 900 | 4.7 | 125 | 455 | 375 | 950 | 350 | 920 | M12 | 10 |
| SHF-0110-10% | C | 110 | 55 | 52.5 | 996 | 5.2 | 140 | 455 | 375 | 950 | 350 | 920 | M12 | 16 |
| SHF-0150-10% | C | 150 | 75 | 71.6 | 1045 | 5.5 | 170 | 455 | 375 | 950 | 350 | 920 | M12 | 25 |
| SHF-0180-10% | C | 180 | 90 | 86 | 1200 | 6.3 | 195 | 455 | 375 | 950 | 350 | 920 | M12 | 25 |
| SHF-0220-10% | C | 220 | 110 | 105 | 1385 | 7.2 | 215 | 485 | 415 | 1085 | 375 | 1055 | M12 | 35 |
| SHF-0260-10% | C | 260 | 132 | 124.1 | 1490 | 7.7 | 245 | 485 | 415 | 1085 | 375 | 1055 | M12 | 50 |
| SHF-0320-10% | C | 320 | 160 | 152.8 | 1565 | 8.1 | 300 | 485 | 415 | 1085 | 375 | 1055 | M12 | 70 |
| SHF-0400-10% | D | 400 | 200 | 190.9 | 1935 | 9.9 | 384 | 485 | 485 | 1230 | 187.5×2 | 1200 | M12 | 95 |
| SHF-0480-10% | D | 480 | 250 | 229.2 | 2282 | 10.5 | 417 | 525 | 485 | 1400 | 207.5×2 | 1370 | M12 | 95 |
| SHF-0600-10% | Cabinet | 600 | 315 | 267.4 | 2766 | 12.8 | 500 | 800 | 800 | 2000 | / | / | — | / |
* Confirm: this individual value requires engineering confirmation before selection or ordering.
Outline and mounting dimensions

Discuss your drive system
Get the right accessory for your application
Send the drive model, voltage, rated current and project requirements. For motor-side filters, include the switching frequency and motor-cable length; for input-side harmonic filtering, include the rectifier type and harmonic target.