INOMAX · VFD Accessories
Motor-side filtering · 1% impedance · Induction-motor drives
INOMAX SOCL output reactors are installed between a VFD and an induction motor. They suppress higher-order harmonics associated with switching-frequency ripple and reduce voltage transients caused by reflections along motor cables. This helps reduce motor eddy-current losses and noise while protecting winding insulation.
Power, voltage and current range
| Configuration | Power reference kW | Rated current A | Models |
|---|---|---|---|
| 400 V · SOCL · 1% impedance | 2.2–630 | 5–1200 | 24 |
| 690 V · SOCL · 1% impedance | 15–1200 | 20–1400 | 17 |
| 690 V · FOCL for explosion-proof VFD assemblies | 75–1200 | 90–1400 | 13 |
| 1140 V · FOCL for explosion-proof VFD assemblies | 160–1200 | 110–800 | 11 |
Choose the applicable configuration below. Voltage, current and power ranges vary by series and are not interchangeable across all models.
Application and connection

Reduce switching ripple
Output-side inductance reduces higher-order harmonic components associated with VFD switching.
Protect motor insulation
Reduce dV/dt transients caused by reflections along motor cables.
Reduce motor losses and noise
Help reduce eddy-current losses and motor noise associated with the PWM supply.
Choose the right output solution
SOCL reactors are the economical output-side option for motor cables up to 150 m; longer routes may call for dV/dt or sine-wave filtering.
Technical specifications
| Parameter | Specification |
|---|---|
| Rated voltage / frequency | 3-phase AC 400 V / 690 V / 1140 V; 50 Hz |
| Insulation class | F / H, depending on series |
| Noise level | ≤75 dB |
| Dielectric strength | AC 3000 V / AC 4200 V, 50 Hz, 5 s; leakage current ≤5 mA |
| Ambient temperature | −25°C to +55°C; up to +75°C for the specified explosion-proof-drive version |
| Referenced standards | GB/T 1094.6-2011; IEC 289:1987; GB/T 19212.1-2023 |
FACL / FOCL data apply to the stated two-quadrant explosion-proof VFD assemblies, with class H insulation and a stated rated temperature rise of ≤70–80 K. Confirm the complete assembly requirements for the application.
Choose the output-side filter
| Solution | Purpose / rating | Stated motor-cable range |
|---|---|---|
| SOCL output reactor | 1% impedance; economical ripple and transient reduction | Up to 150 m |
| DUT dV/dt filter | Peak voltage ≤1000 / 1800 V; dV/dt ≤300 V/µs | Up to 400 m unshielded |
| DVT dV/dt filter | 400 V range; peak voltage ≤1000 V; dV/dt ≤300 V/µs | Up to 950 m unshielded |
| SLB sine-wave filter | Near-sinusoidal output waveform | Confirm for the selected drive, filter and cable |
| VSA peak absorber | Peak-voltage suppression, ≤1000 / 1800 V by system | Up to 950 m |
| LCM sine conditioner | THDv / THDi ≤5% | 400–950 m |
DUT, DVT and SLB details are available through the related-product links below. VSA and LCM are additional solution options; request application-specific selection.
Model selection and installation data
Match motor current, voltage, VFD switching frequency and motor cable length. The maximum switching frequency varies by model. For cables beyond the SOCL selection range, compare DUT, DVT and SLB filtering solutions.
65 model ratings shown
Expand a configuration to compare models. On a phone, swipe the table horizontally to see all dimensions.
400 V · SOCL · 1% impedance · 24 models
| Model | Figure | Switching ≤ kHz | Drive kW | Rated A | Inductance mH | Weight kg | W mm | D mm | H mm | W0 mm | D0 mm | A×B mm |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SOCL-0005-EISC-140B | A | 5 | 2.2 | 5 | Confirm* | 1.5 | 95 | 69 | 110 | 40 | 48 | 7×11 |
| SOCL-0010-EISC-700C | A | 5 | 3.7 | 10 | 0.7 | 2.6 | 115 | 76 | 125 | 50 | 53 | 7×11 |
| SOCL-0013-EISC-540C | A | 5 | 5.5 | 13 | 0.54 | 2.8 | 115 | 76 | 125 | 50 | 53 | 7×11 |
| SOCL-0016-EISC-438C | A | 5 | 7.5 | 16 | 0.438 | 2.9 | 115 | 76 | 125 | 50 | 53 | 7×11 |
| SOCL-0025-EISC-280C | B | 4 | 11 | 25 | 0.28 | 5.3 | 150 | 100 | 190 | 60 | 67 | 7×11 |
| SOCL-0030-EISC-233C | B | 4 | 15 | 30 | 0.233 | 5.6 | 150 | 100 | 190 | 60 | 67 | 7×11 |
| SOCL-0045-EISA-155C | C | 4 | 22 | 45 | 0.155 | 5.8 | 180 | 110 | 160 | 80 | 67 | 7×11 |
| SOCL-0060-EISA-117C | C | 3 | 30 | 60 | 0.117 | 8.4 | 180 | 130 | 160 | 80 | 87 | 7×11 |
| SOCL-0075-EISA-935D | C | 3 | 37 | 75 | 0.0935 | 8.7 | 180 | 130 | 160 | 80 | 87 | 7×11 |
| SOCL-0090-EISA-785D | C | 3 | 45 | 90 | 0.0785 | 8.9 | 180 | 130 | 160 | 80 | 87 | 7×11 |
| SOCL-0110-EISA-640D | C | 3 | 55 | 110 | 0.064 | 14.4 | 230 | 160 | 220 | 110 | 85 | 9×18 |
| SOCL-0150-EISA-467D | C | 3 | 75 | 150 | 0.0467 | 15.0 | 230 | 160 | 220 | 110 | 85 | 9×18 |
| SOCL-0180-EISA-390D | C | 3 | 90 | 180 | 0.039 | 19.2 | 230 | 175 | 220 | 110 | 100 | 9×18 |
| SOCL-0220-EISA-320D | C | 3 | 110 | 220 | 0.032 | 20.3 | 230 | 175 | 220 | 110 | 100 | 9×18 |
| SOCL-0260-EISA-270D | D | 3 | 132 | 260 | 0.027 | 26.5 | 260 | 185 | 265 | 140 | 110 | 9×18 |
| SOCL-0320-EISA-220D | D | 3 | 160 | 320 | 0.022 | 27.7 | 260 | 185 | 265 | 140 | 110 | 9×18 |
| SOCL-0400-EISA-175D | D | 3 | 200 | 400 | 0.0175 | 33.1 | 300 | 205 | 280 | 170 | 110 | 11×18 |
| SOCL-0480-EISA-145D | D | 3 | 250 | 480 | 0.0145 | 45.0 | 300 | 230 | 280 | 170 | 135 | 11×18 |
| SOCL-0540-EISA-130D | D | 3 | 280 | 540 | 0.013 | 45.8 | 300 | 230 | 280 | 170 | 135 | 11×18 |
| SOCL-0600-EISA-117D | D | 3 | 315 | 600 | 0.0117 | 46.8 | 300 | 230 | 280 | 170 | 135 | 11×18 |
| SOCL-0800-EISA-875E | D | 2 | 400 | 800 | 0.00875 | 66.0 | 360 | 265 | 375 | 190 | 135 | 13×26 |
| SOCL-1000-EISA-700E | D | 2 | 500 | 1000 | 0.007 | 69.3 | 360 | 265 | 375 | 190 | 135 | 13×26 |
| SOCL-1100-EISA-635E | E | 2 | 560 | 1100 | 0.00635 | 98.0 | 430 | 305 | 410 | 240 | 175 | 14×28 |
| SOCL-1200-EISA-585E | E | 2 | 630 | 1200 | 0.00585 | 100.0 | 430 | 305 | 410 | 240 | 175 | 14×28 |
690 V · SOCL · 1% impedance · 17 models
| Model | Figure | Switching ≤ kHz | Drive kW | Rated A | Inductance mH | Weight kg | W mm | D mm | H mm | W0 mm | D0 mm | A×B mm |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SOCL-0020-EISC-640C | B | 2 | 15 | 20 | 0.64 | 5.4 | 150 | 100 | 190 | 60 | 67 | 7×11 |
| SOCL-0030-EISC-425C | B | 2 | 22 | 30 | 0.425 | 8.7 | 180 | 110 | 220 | 80 | 87 | 7×11 |
| SOCL-0045-EISA-283C | C | 2 | 37 | 45 | 0.283 | 12.7 | 230 | 160 | 190 | 110 | 85 | 9×18 |
| SOCL-0060-EISA-212C | C | 2 | 45 | 60 | 0.212 | 14.6 | 230 | 160 | 220 | 110 | 85 | 9×18 |
| SOCL-0090-EISA-141C | C | 2 | 75 | 90 | 0.141 | 15.4 | 230 | 160 | 220 | 110 | 85 | 9×18 |
| SOCL-0110-EISA-115C | C | 2 | 90 | 110 | 0.115 | 20.1 | 230 | 175 | 220 | 110 | 100 | 9×18 |
| SOCL-0150-EISA-850D | C | 2 | 110 | 150 | 0.085 | 20.8 | 230 | 175 | 220 | 110 | 100 | 9×18 |
| SOCL-0200-EISA-640D | D | 2 | 160 | 200 | 0.064 | 28.7 | 260 | 185 | 265 | 140 | 110 | 9×18 |
| SOCL-0250-EISA-510D | D | 2 | 200 | 250 | 0.051 | 30.6 | 260 | 185 | 265 | 140 | 110 | 9×18 |
| SOCL-0300-EISA-425D | D | 2 | 250 | 300 | 0.0425 | 36.8 | 300 | 200 | 280 | 170 | 110 | 11×18 |
| SOCL-0400-EISA-320D | D | 1.5 | 355 | 400 | 0.032 | 48.9 | 300 | 225 | 280 | 170 | 135 | 11×18 |
| SOCL-0480-EISA-265D | D | Confirm* | 450 | 480 | 0.0265 | 68.8 | 360 | 250 | 375 | 190 | 135 | 13×26 |
| SOCL-0600-EISA-213D | D | 1.5 | 560 | 600 | 0.0213 | 71.1 | 360 | 250 | 375 | 190 | 135 | 13×26 |
| SOCL-0800-EISA-160D | E | 1.5 | 710 | 800 | 0.016 | 100.5 | 430 | 290 | 410 | 240 | 175 | 14×28 |
| SOCL-1000-EISA-127D | E | 1.5 | 900 | 1000 | 0.0127 | 100.6 | 430 | 290 | 410 | 240 | 175 | 14×28 |
| SOCL-1100-EISA-115D | E | 1.5 | 1000 | 1100 | 0.0115 | 134.8 | 430 | 320 | 520 | 240 | 190 | 14×28 |
| SOCL-1400-EISA-900E | E | 1.5 | 1200 | 1400 | 0.009 | 144.5 | 430 | 320 | 520 | 240 | 190 | 14×28 |
690 V · FOCL for explosion-proof VFD assemblies · 13 models
| Model | Figure | Switching ≤ kHz | Drive kW | Rated A | Inductance mH | Weight kg | W mm | D mm | H mm | W0 mm | D0 mm | A×B mm |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| FOCL-0090-EISC-141C | C | 2 | 75 | 90 | 0.141 | 18.1 | 230 | 145 | 220 | 110 | 85 | 9×18 |
| FOCL-0110-EISC-115C | C | 2 | 90 | 110 | 0.115 | 21.5 | 230 | 160 | 220 | 110 | 100 | 9×18 |
| FOCL-0150-EISC-850D | C | 2 | 110 | 150 | 0.085 | 24.4 | 230 | 170 | 220 | 110 | 100 | 9×18 |
| FOCL-0200-EISC-640D | D | 2 | 160 | 200 | 0.064 | 32.4 | 260 | 180 | 265 | 140 | 110 | 9×18 |
| FOCL-0250-EISC-510D | D | 2 | 200 | 250 | 0.051 | 37.9 | 260 | 180 | 265 | 140 | 110 | 9×18 |
| FOCL-0300-EISC-425D | D | 2 | 250 | 300 | 0.0425 | 45.4 | 300 | 185 | 280 | 170 | 110 | 11×18 |
| FOCL-0400-EISC-320D | D | 1.5 | 355 | 400 | 0.032 | 59.7 | 300 | 225 | 280 | 170 | 135 | 11×18 |
| FOCL-0480-EISC-265D | D | 1.5 | 450 | 480 | 0.0265 | 76.8 | 360 | 245 | 375 | 190 | 135 | 13×26 |
| FOCL-0600-EISC-213D | D | 1.5 | 560 | 600 | 0.0213 | 86.2 | 360 | 245 | 375 | 190 | 135 | 13×26 |
| FOCL-0800-EISC-160D | E | 1.5 | 710 | 800 | 0.016 | 107.6 | 430 | 280 | 410 | 240 | 175 | 14×28 |
| FOCL-1000-EISC-127D | E | 1.5 | 900 | 1000 | 0.0127 | 118.7 | 430 | 280 | 410 | 240 | 175 | 14×28 |
| FOCL-1100-EISC-115D | E | 1.5 | 1000 | 1100 | 0.0115 | 149.2 | 430 | 300 | 520 | 240 | 190 | 14×28 |
| FOCL-1400-EISC-900E | E | 1.5 | 1200 | 1400 | 0.009 | 166.4 | 430 | 320 | 520 | 240 | 190 | 14×28 |
1140 V · FOCL for explosion-proof VFD assemblies · 11 models
| Model | Figure | Switching ≤ kHz | Drive kW | Rated A | Inductance mH | Weight kg | W mm | D mm | H mm | W0 mm | D0 mm | A×B mm |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| FOCL-0110-EISC-190C | D | 2 | 160 | 110 | 0.19 | 33.8 | 260 | 180 | 275 | 140 | 110 | 9×18 |
| FOCL-0150-EISC-140C | D | 2 | 200 | 150 | 0.14 | 40.1 | 260 | 180 | 275 | 140 | 110 | 9×18 |
| FOCL-0200-EISC-105C | D | 2 | 280 | 200 | 0.105 | 48.8 | 300 | 180 | 290 | 170 | 110 | 11×18 |
| FOCL-0250-EISC-840D | D | 1.5 | 355 | 250 | 0.084 | 63.2 | 300 | 205 | 290 | 170 | 135 | 11×18 |
| FOCL-0300-EISC-700D | D | Confirm* | 450 | 300 | 0.07 | 78.7 | 360 | 215 | 375 | 190 | 135 | 13×26 |
| FOCL-0350-EISC-600D | D | 1.5 | 500 | 350 | 0.06 | 85.0 | 360 | 215 | 375 | 190 | 135 | 13×26 |
| FOCL-0400-EISC-525D | D | 1.5 | 630 | 400 | 0.0525 | 85.3 | 360 | 225 | 375 | 190 | 135 | 13×26 |
| FOCL-0480-EISC-438D | E | 1.5 | 710 | 480 | 0.0438 | 118.7 | 430 | 250 | 410 | 240 | 175 | 14×28 |
| FOCL-0600-EISC-350D | E | 1.5 | 900 | 600 | 0.035 | 124.4 | 430 | 250 | 410 | 240 | 175 | 14×28 |
| FOCL-0700-EISC-300D | E | 1.5 | 1000 | 700 | 0.03 | 156.5 | 430 | 295 | 520 | 240 | 190 | 14×28 |
| FOCL-0800-EISC-263D | E | 1.5 | 1200 | 800 | 0.0263 | 171.9 | 430 | 295 | 520 | 240 | 190 | 14×28 |
* Confirm: this individual value requires engineering confirmation before selection or ordering.
Copper-wound EISC versions may be slightly heavier; confirm the final weight for the selected winding construction. A/B/C are three-phase input terminals; X/Y/Z are three-phase output terminals.
Outline and mounting dimensions

Discuss your drive system
Get the right accessory for your application