Product overview
AST6200 combines online motor starting with standard RS485 Modbus RTU, external command inputs, relay outputs and 4–20 mA feedback. This product configuration is aimed at system integrators connecting a motor starter to a PLC, HMI or supervisory control system. Select the power unit by motor voltage, rated current and duty independently of the communication design.

Control modes and command ownership
Parameter A00 selects local, external-terminal and communication control, including supported combinations. Define which station is allowed to issue a start or stop command and how the installation handles a communication interruption. Commission the selected mode against the complete machine sequence; the existence of a Modbus link does not by itself establish remote-control readiness.
Modbus RTU interface
| Item | V2612 manual specification |
|---|---|
| Physical interface | RS485, half duplex |
| Protocol | Modbus RTU |
| Data format | 8 data bits, no parity, 1 stop bit (8N1) |
| Device address | 1–127 |
| Baud rates | 2400, 4800, 9600 or 19200 bit/s; default 9600 |
| Supported functions | 03: read holding registers; 06: write a single register |
| Integration reference | Use the register map and command definitions in the supplied manual |
Match address, baud rate and data format at both ends. Use the documented register addresses, scaling and allowed commands for the applicable manual version. Do not infer Ethernet, PROFINET, PROFIBUS or EtherCAT support from the standard RS485 interface.
Terminal and feedback planning
| Interface | Planning requirement |
|---|---|
| Running relay | One running relay output for the defined running indication |
| Programmable relays | Two programmable relay outputs; select the required function and delay |
| Analog output | 4–20 mA feedback; confirm the selected signal and receiving-channel scaling |
| External fault input | Terminal 7; the manual requires connection to common terminal 10 for normal operation |
| External commands | Terminal 8 stop, terminal 9 start, terminal 10 common; use the manual circuit |
| RS485 terminals | 13 (+) and 14 (−), as shown in V2612 |
| Optional control supply | A1/A2 external 220–440 VAC control supply is an order option; confirm before wiring |
This table supports interface planning and does not replace the wiring diagrams. Have qualified personnel verify the delivered unit, terminal identification, isolation and control-circuit design before energizing.
Monitoring and fault handling
The removable LCD and monitoring functions expose three-phase current, input and output voltage, starting status, supply frequency, phase sequence, current unbalance, accumulated operation information and fault records as documented. Establish the PLC/HMI indication needed by the operator and distinguish a start command from confirmed running status.
Review fault responses and reset conditions. V2612 permits configurable handling; starting overcurrent and underload default to Ignore. Commission overload, current, voltage, phase and thermal functions against the motor and process requirements instead of treating every factory setting as a completed protection study.
Integration acceptance checklist
- Confirm exact AST6200 model and applicable firmware/manual version.
- Verify the communication settings and read known status values with the motor stopped.
- Confirm command ownership, normal start/stop and the running-status response in a controlled commissioning procedure.
- Verify signal scaling, programmable relay functions and fault/reset handling.
- Document final parameters, panel wiring and the intended response to loss of communication.
Choose the voltage and current class
| Voltage class | Three-phase supply | Catalog power range | Rated current range |
|---|---|---|---|
| S4 | 380–480 V | 7.5–800 kW | 17–1600 A |
| S2 | 220–240 V | 5.5–400 kW | 23–1400 A |
| S6 | 520–690 V | 7.5–1400 kW | 11–1600 A |
| S11 | 1000–1140 V | 15–800 kW | 10–560 A |
Start from the actual motor nameplate, not only the machine power. Ratings differ by voltage class. Confirm load torque, acceleration, repeated starts and any environmental derating with INOMAX.
Custom cabinet-type soft starter
INOMAX can supply AST6200 as a custom cabinet-type soft starter for project, system-integrator and OEM requirements. For a PLC-controlled cabinet, agree the Modbus RTU interface, hardwired interlocks and the required running and fault feedback.
Specify the required enclosure protection, installation environment, incoming isolation and protection, door controls, cable entry and cooling arrangement. Cabinet dimensions, component selection and supply scope are confirmed for the quoted configuration. The IP20 rating and dimensions in a standard AST6200 datasheet describe the starter unit, not the completed cabinet.

Download a datasheet by voltage and power
Choose the motor supply voltage first, then find its kW reference and compare the starter current with the motor nameplate. Download links show voltage and power as well as the AST6200 model, so the file can be selected without knowing the model code in advance.
- 220–240 V · 5.5–400 kW model datasheets
- 380–480 V · 7.5–800 kW model datasheets
- 520–690 V · 7.5–1400 kW model datasheets
- 1000–1140 V · 15–800 kW model datasheets
These PDFs describe individual starter units. For a custom cabinet, request the agreed cabinet specification and controlled dimensional drawing from info@inomaxtechnology.com.
Frequently asked questions
Is Modbus RTU standard?
Yes. The V2612 documentation lists RS485 Modbus RTU as standard. Confirm any project-specific interface requirements before ordering.
Can a PLC read operating information?
The manual provides a Modbus register map. Use its definitions and scaling for the applicable unit version and validate the values during commissioning.
Does this page specify a safety communication system?
No. Standard communication, relays and command terminals do not establish safety-rated control. Define the machine safety architecture separately.
Catalog, manual and selection support
AST6200 English Catalog — V2612 (PDF) · AST6200 User Manual — V2612 (PDF)
Specifications on this page refer to these AST6200 editions. Use the supplied unit nameplate and applicable manual for final installation and commissioning. Download the selected model datasheet using the voltage and power links above. Ask INOMAX for the controlled dimensional drawing and agreed cabinet specification before fabrication.
Soft starter selection for pumps, fans and heavy loads · Browse all AST6200 product options
Specify your AST6200
Send the motor nameplate, application and starts per hour. INOMAX can review the voltage class, current rating, control requirements and cabinet arrangement before quotation.
Email: info@inomaxtechnology.com. Confirm warranty coverage, support scope, availability and delivery schedule for the quoted model and destination.