← MAX-MV series overview · Explore all 10 selection guides
01 · Product overview
A practical drive platform for large industrial utilities.
MAX-MV 6 kV and 6.6 kV drives support motor-driven pumps, fans, compressors and process equipment in power generation, cement, metals and mining. A cascaded modular power stage produces the medium-voltage output, while a DSP/FPGA controller coordinates motor regulation, cell operation and protection.
For an EPC contractor or system integrator, the key decision is how the drive fits the plant operating duty. Starting a high-inertia fan, controlling a circulation pump and operating a constant-torque compressor place different demands on current, acceleration, feedback and availability. These requirements determine the drive selection and options.
02 · Rating and cabinet selection
Power, voltage and current selection
Match the motor nameplate current, overload duty and site derating before confirming a model. The filters below help you compare the listed selections; final cabinet and option details are agreed for the project.
64 reference selections
No matching selection in this table. Send your motor data for engineering review.
Dimensions exclude top fans, bypass additions and service clearances. At 6.6 kV from 2,800 kW and 11 kV from 4,500 kW, add an 800 mm current-limiting cabinet with matching depth and height. Use the approved project drawing for the complete installation.
03 · Application fit
Application requirements that shape the package
Power and heating utilities
Induced-draft fans, primary-air fans, condensate pumps and circulation systems. Define permitted process interruption and restart sequences.
Cement, steel and mining
Kiln and mill ventilation, dust extraction, mine ventilation and drainage. Match the enclosure and cooling system to the actual electrical room.
Process compressors and pumps
Continuous or heavy-duty machinery. Provide starting torque, speed limits and the process interlock list for motor-control selection.
04 · Integration and options
Functions, accessories and engineering decisions
Allow for high-inertia starting
Adjustable acceleration of 0.1–3,600 s supports application-specific ramps. The motor must still develop enough accelerating torque without exceeding the permitted current or thermal duty. Supply the inertia, load torque and acceptable starting time for large fans.
Choose a continuity strategy
Cell bypass, line bypass, redundant controllers and a standby drive address different failures. Define the minimum acceptable speed and output after a cell fault, whether direct-line operation is possible, and the restart conditions accepted by the plant.
Include the current-limiting cabinet when required
For 6.6 kV selections from 2,800 kW inclusive, allow an additional 800 mm current-limiting cabinet with matching depth and height. Base cabinet dimensions alone do not describe the installed footprint. Larger 6 kV projects also need an incoming-network and inrush review.
Coordinate protection and the DCS
Agree the upstream switchgear interface, trip and close-permission signals, speed reference, process feedback and alarm handling. Standard Modbus RTU and I/O can support integration; optional networking and redundant-control arrangements must be defined in the equipment scope.
Define the equipment scope
| Configuration item | What to agree |
|---|---|
| Motor control and feedback | Motor technology, control mode and encoder interface where required |
| Bypass / isolation | Manual or automatic line bypass, isolation and switching interlocks; selected for the process |
| Control integration | Standard Modbus RTU / I/O; optional PROFIBUS DP or exact TCP/IP arrangement |
| Continuity options | Cell-bypass strategy, controller redundancy or standby drive as project-selected |
| Service package | Spare cells, fans, boards, commissioning and training scope |
05 · Electrical performance
Performance for a defined operating duty
| Performance item | Selection basis |
|---|---|
| Motor-control modes | V/F; V/F with feedback; sensorless vector; closed-loop vector |
| Overload capability | 120% for 120 s; 150% for 5 s, checked against selected configuration and duty |
| Frequency resolution | 0.01 Hz; resolution is distinct from motor-speed accuracy |
| Acceleration / deceleration | 0.1–3,600 s; set within motor and process limits |
| Inverter efficiency | 98.5%; excludes the phase-shifting transformer |
| Power factor | ≥0.96 at the specified operating conditions |
| Harmonic performance | THD ≤4% for 3–4.16 kV; ≤2% for 6–13.8 kV. Confirm measurement point, loading and network conditions. |
Confirm performance at the required motor duty, supply conditions and cooling arrangement. For regenerative or braking loads, specify the operating cycle so a suitable two- or four-quadrant power stage can be selected.
06 · Technical data
Installation, environment and maintenance
| Item | Requirement / configuration |
|---|---|
| Operating temperature | −10 to +40°C; higher temperature requires an approved cooling and derating plan |
| Humidity | 20–90% RH, non-condensing, as the installation basis; confirm higher-humidity configurations |
| Altitude | Provide the site elevation; above 1,000 m, review insulation, cooling and derating for the selected configuration |
| Storage | −40 to +70°C; dry, protected storage without condensation or outdoor exposure |
| Cooling and enclosure | Forced air or water cooling; IP31 standard, IP42 optional, custom IP54 |
| Control supply | 220 V AC, 3 kVA, 50/60 Hz; optional DC supply by project arrangement |
| Control interfaces | 3 analog inputs / 4 analog outputs; 8 digital inputs / 5 digital outputs; RS485 / Modbus RTU standard |
| Installation | Indoor electrical room; no explosive/corrosive gases, conductive dust or oil mist; keep cooling and service access clear |
Plan safe service access, delivery openings, foundation loading and separate power/control cable routes. Inspection intervals and replacement work follow the installed equipment manual and the site maintenance plan.
07 · Supplier and configuration comparison
Compare complete proposals on the same basis
| Comparison point | What to check |
|---|---|
| Starting performance | Compare the same motor inertia, start time and overload duty. |
| Availability | Compare output after cell bypass and the actual standby/transfer arrangement. |
| Installed footprint | Include transformer, bypass, current limiting, top fans and service access. |
| Grid integration | Confirm source capacity, inrush, harmonics and upstream protection coordination. |
Ask each supplier to identify inclusions, exclusions and deviations. The selected rating, options, installation work, acceptance test and service responsibilities should be clear before comparing the final price.
08 · Customer applications
Relevant industrial project experience
Reciprocating compressor
MAX-MV-060-400-050
A 6 kV compressor configuration is recorded for the Daqing Zhongrui Gas 500,000 m³ LNG project, with an outdoor-type arrangement.
High-pressure water injection
MAX-MV-060-1400
The Weicheng water-injection station project used a 6 kV, 1,400 kW drive selection for a large-flow reciprocating pump, with an outdoor arrangement.
Discuss a comparable configuration with INOMAX. The motor, equipment scope and operating conditions are assessed separately for each project.
Practical project FAQ
Questions to resolve before ordering
6 questions
Which MAX-MV model is suitable for a 6.6 kV 2 MW motor?
MAX-MV-066-2000 is a 2,000 kW reference selection with 219 A current and a 3200 × 1550 × 2200 mm base cabinet. Confirm the motor nameplate current, overload and site derating before final selection.
Why can a 6.6 kV cabinet need more space than a 6 kV cabinet?
The cell arrangement and cabinet dimensions vary with voltage and rating. At 6.6 kV, selections from 2,800 kW also require an additional 800 mm current-limiting cabinet. Compare the complete approved layouts rather than assuming equal power means equal dimensions.
Can the drive restart a fan that is still rotating?
Flying start identifies a motor that is rotating forward, rotating in reverse or stationary before bringing it to the target frequency. Enable the function only with the machine and process restart permissions agreed; it is not a substitute for plant interlocking.
Will a short power interruption stop our process?
MAX-MV provides voltage ride-through and restart functions, but the result depends on the depth and duration of the disturbance, motor inertia, load and settings. Define the actual supply disturbance and minimum acceptable process speed for an engineering review.
Does power-cell bypass mean the drive remains at full output?
Not necessarily. Bypassing cells can reduce available output voltage and therefore the permitted motor operating point. Agree the number of bypassed cells, bypass strategy and required load capability in the technical specification.
Can an EPC obtain drawings and a witnessed factory test?
Drawings, interface schedules and a project-specific acceptance test can be included in the proposal. Agree document revisions, test scope, witness arrangements and acceptance criteria before manufacture so these become planned delivery milestones.
No matching question. Ask our application team.
Technical resources
Catalog, manual & project support
MAX-MV catalog
Ratings, dimensions, features and configuration options.
MAX-MV user manual
Installation, operation, control settings and maintenance.
Project-specific documents
Contact INOMAX for project records, drawings, certificates and test reports matched to your application.
09 · Start the conversation
Let’s define your next MAX-MV project.
Request a 6 / 6.6 kV Proposal
Share the motor current, load inertia, process-continuity requirement and electrical-room layout for a coordinated drive proposal.
Email: info@inomaxtechnology.com
Build your local MAX-MV business
Discuss the industries you serve, application-engineering support, training, commissioning and spare-parts planning. Commercial and service arrangements are defined for your market and projects.