Product overview
AST6200 is an online soft starter for three-phase fan and blower motors where the required process speed is the motor operating speed at the connected supply frequency. It gives panel builders a choice of starting modes and configurable current and thermal protection for controlled run-up.
Fan inertia and acceleration planning
| Selection point | Application requirement |
|---|---|
| Inertia | Provide the fan or blower inertia and the required acceleration time. A large rotating assembly can extend starting duty even if the motor kW appears modest. |
| Air path | Record damper position, duct conditions and the expected operating condition at start. The actual machine and system determine the load during acceleration. |
| Current limit | The adjustable current-limit setting is 50–600%. Use a setting that can accelerate the load within its thermal limits; the lowest setting is not automatically the best choice. |
| Restart | State coast-down and restart expectations. Review the procedure for a rotating or windmilling fan with the machine supplier and INOMAX before commissioning. |
Functions and performance
| Function | What it provides |
|---|---|
| Starting modes | Voltage ramp, current-limit and torque starting |
| Starting adjustment | Starting time 1–120 s; initial voltage 30–80%; current-limit setting 50–600% |
| Stopping | Free/coast stop or soft stop; soft-stop time 0–60 s |
| Control | Local keypad, external terminals or communication control, with selectable combinations |
| Display | Removable Chinese/English LCD; operating status, current, voltage and fault information |
| Communication | RS485 Modbus RTU as standard |
| Feedback | One running relay, two programmable relay outputs and 4–20 mA analog output |
| Protection | Configurable overload, overcurrent, voltage, phase, unbalance, underload and thermal functions |
Adjustment ranges are parameter limits, not a guarantee that every motor can start at every setting. Starting duty, load torque and the motor thermal limits govern commissioning. Review the protection response settings: starting overcurrent and underload are set to Ignore by default in the V2612 manual.
How to select the AST6200
- Provide the motor nameplate and fan or blower type.
- Add load inertia, intended run-up time and starts per hour.
- Describe damper or inlet control, interlocks and whether the fan can rotate before start.
- Check panel ventilation, altitude and the motor protection response for extended acceleration.
Choose the voltage and current class
| Voltage class | Three-phase supply | Catalog power range | Rated current range |
|---|---|---|---|
| S4 | 380–480 V | 7.5–800 kW | 17–1600 A |
| S2 | 220–240 V | 5.5–400 kW | 23–1400 A |
| S6 | 520–690 V | 7.5–1400 kW | 11–1600 A |
| S11 | 1000–1140 V | 15–800 kW | 10–560 A |
Start from the actual motor nameplate, not only the machine power. Ratings differ by voltage class. Confirm load torque, acceleration, repeated starts and any environmental derating with INOMAX.
Performance checks for a fan panel
Compare the intended acceleration time with measured run-up and current during commissioning. Confirm the transition to normal running, correct phase sequence and suitable protection settings. Retain the final parameters and restart procedure for maintenance staff. No fixed starts-per-hour rating is stated here because permissible duty depends on the motor, load and thermal conditions.
Installation and operating conditions
| Item | AST6200 specification / selection requirement |
|---|---|
| Motor | Three-phase squirrel-cage asynchronous motor |
| Supply frequency | 30–70 Hz supply frequency; this is not a variable output-frequency range |
| Enclosure and cooling | IP20 unit, forced-air cooling, indoor installation |
| Ambient temperature | −10 to +40 °C; confirm suitability outside the specified range |
| Altitude | Below 2,000 m; derating is required above this altitude |
| Humidity and vibration | Below 95% RH, non-condensing; vibration below 0.5 G |
| Panel design | Keep cooling paths clear; exclude conductive dust, corrosive and explosive gases |
| Duty rating | Select by motor rated current, starting time, load and starts per hour |
Provide upstream isolation and protective devices to the installation design. Do not connect capacitors to the soft starter output. Electrical installation and commissioning must follow the manual and applicable site requirements.
Custom cabinet-type soft starter
INOMAX can supply AST6200 as a custom cabinet-type soft starter for project, system-integrator and OEM requirements. For a fan or blower cabinet, provide fan inertia, acceleration time and repeated-start duty for the thermal review.
Specify the required enclosure protection, installation environment, incoming isolation and protection, door controls, cable entry and cooling arrangement. Cabinet dimensions, component selection and supply scope are confirmed for the quoted configuration. The IP20 rating and dimensions in a standard AST6200 datasheet describe the starter unit, not the completed cabinet.

Download a datasheet by voltage and power
Choose the motor supply voltage first, then find its kW reference and compare the starter current with the motor nameplate. Download links show voltage and power as well as the AST6200 model, so the file can be selected without knowing the model code in advance.
- 220–240 V · 5.5–400 kW model datasheets
- 380–480 V · 7.5–800 kW model datasheets
- 520–690 V · 7.5–1400 kW model datasheets
- 1000–1140 V · 15–800 kW model datasheets
These PDFs describe individual starter units. For a custom cabinet, request the agreed cabinet specification and controlled dimensional drawing from info@inomaxtechnology.com.
Frequently asked questions
Can the 1–120 s setting cover every large fan?
No. That is the available starting-time parameter range. The motor, starter and load must be evaluated for the actual acceleration current and thermal duty.
Does it adjust fan speed during operation?
AST6200 is a soft starter. Use a VFD when continuous speed regulation is required.
Can a fan restart while still rotating?
Provide the rotation and restart conditions for engineering review. Do not assume a stationary-load setting is suitable for a rotating fan.
Catalog, manual and selection support
AST6200 English Catalog — V2612 (PDF) · AST6200 User Manual — V2612 (PDF)
Specifications on this page refer to these AST6200 editions. Use the supplied unit nameplate and applicable manual for final installation and commissioning. Download the selected model datasheet using the voltage and power links above. Ask INOMAX for the controlled dimensional drawing and agreed cabinet specification before fabrication.