01 · Product overview
A medium-voltage drive for your motor voltage.
MAX-MV uses a phase-shifting transformer and cascaded power cells to control large AC motors directly at medium voltage. For a pump builder, fan OEM or local distributor, the first selection is the actual motor voltage: 3 kV, 3.3 kV and 4.16 kV are separate equipment ratings, even when the motor power is identical.
The transformer, cell arrangement, protection and cabinet layout are coordinated as a complete drive package. Induction motors are the standard selection; synchronous and permanent-magnet synchronous motor configurations require the corresponding motor data and control arrangement. Specify whether the motor will run continuously at variable speed or only needs a starting solution.
02 · Rating and cabinet selection
Power, voltage and current selection
Match the motor nameplate current, overload duty and site derating before confirming a model. The filters below help you compare the listed selections; final cabinet and option details are agreed for the project.
77 reference selections
No matching selection in this table. Send your motor data for engineering review.
Dimensions exclude top fans, bypass additions and service clearances. At 6.6 kV from 2,800 kW and 11 kV from 4,500 kW, add an 800 mm current-limiting cabinet with matching depth and height. Use the approved project drawing for the complete installation.
03 · Application fit
Application requirements that shape the package
Pumps and water systems
Intake, transfer, circulation and process pumps that need flow or pressure control. Provide the system curve, static head and minimum permitted flow.
Industrial fans and blowers
Ventilation, dust extraction and process-air duties. Match acceleration time and flying-start behaviour to fan inertia and possible reverse rotation.
OEM machinery and retrofits
Motor-driven packages and existing installations using 3.3 or 4.16 kV supplies. Coordinate the drive with the machine controls, motor insulation and available electrical-room space.
04 · Integration and options
Functions, accessories and engineering decisions
Compare current, not just motor kW
A 1,000 kW reference selection is 240 A at 3 kV, 219 A at 3.3 kV and 170 A at 4.16 kV. Check the actual nameplate current, overload cycle and environmental derating before choosing the final drive. These figures should not be converted into one universal 1 MW model.
Separate the incoming supply from the motor rating
Record both voltages and the 50/60 Hz supply frequency. A voltage mismatch needs an engineered transformer and output arrangement. If line bypass is requested, separately check that the motor can accept the bypass supply voltage and starting method.
Build the control interface with the OEM
Select V/F, sensorless vector or encoder-based vector control to suit the load. Standard RS485 / Modbus RTU and configurable analog/digital signals provide the basic plant interface; optional PROFIBUS DP or TCP/IP networking must be specified by exact protocol and signal map.
Plan access around the entire cabinet
The selection table gives the base cabinet dimensions. Add the selected bypass equipment, top fans, cable-entry space and service access. Discuss transport sections and lifting before the electrical-room layout is frozen.
Define the equipment scope
| Configuration item | What to agree |
|---|---|
| Motor control and feedback | Motor technology, control mode and encoder interface where required |
| Bypass / isolation | Manual or automatic line bypass, isolation and switching interlocks; selected for the process |
| Control integration | Standard Modbus RTU / I/O; optional PROFIBUS DP or exact TCP/IP arrangement |
| Continuity options | Cell-bypass strategy, controller redundancy or standby drive as project-selected |
| Service package | Spare cells, fans, boards, commissioning and training scope |
05 · Electrical performance
Performance for a defined operating duty
| Performance item | Selection basis |
|---|---|
| Motor-control modes | V/F; V/F with feedback; sensorless vector; closed-loop vector |
| Overload capability | 120% for 120 s; 150% for 5 s, checked against selected configuration and duty |
| Frequency resolution | 0.01 Hz; resolution is distinct from motor-speed accuracy |
| Acceleration / deceleration | 0.1–3,600 s; set within motor and process limits |
| Inverter efficiency | 98.5%; excludes the phase-shifting transformer |
| Power factor | ≥0.96 at the specified operating conditions |
| Harmonic performance | THD ≤4% for 3–4.16 kV; ≤2% for 6–13.8 kV. Confirm measurement point, loading and network conditions. |
Confirm performance at the required motor duty, supply conditions and cooling arrangement. For regenerative or braking loads, specify the operating cycle so a suitable two- or four-quadrant power stage can be selected.
06 · Technical data
Installation, environment and maintenance
| Item | Requirement / configuration |
|---|---|
| Operating temperature | −10 to +40°C; higher temperature requires an approved cooling and derating plan |
| Humidity | 20–90% RH, non-condensing, as the installation basis; confirm higher-humidity configurations |
| Altitude | Provide the site elevation; above 1,000 m, review insulation, cooling and derating for the selected configuration |
| Storage | −40 to +70°C; dry, protected storage without condensation or outdoor exposure |
| Cooling and enclosure | Forced air or water cooling; IP31 standard, IP42 optional, custom IP54 |
| Control supply | 220 V AC, 3 kVA, 50/60 Hz; optional DC supply by project arrangement |
| Control interfaces | 3 analog inputs / 4 analog outputs; 8 digital inputs / 5 digital outputs; RS485 / Modbus RTU standard |
| Installation | Indoor electrical room; no explosive/corrosive gases, conductive dust or oil mist; keep cooling and service access clear |
Plan safe service access, delivery openings, foundation loading and separate power/control cable routes. Inspection intervals and replacement work follow the installed equipment manual and the site maintenance plan.
07 · Supplier and configuration comparison
Compare complete proposals on the same basis
| Comparison point | What to check |
|---|---|
| Voltage suitability | Same incoming supply and motor voltage, including tolerances and frequency. |
| Motor duty | Continuous current, overload duration, acceleration and minimum operating speed. |
| Complete scope | Transformer, bypass, cooling equipment, control supply, testing and commissioning. |
| Lifecycle support | Identified spare modules, local service arrangements and warranty scope. |
Ask each supplier to identify inclusions, exclusions and deviations. The selected rating, options, installation work, acceptance test and service responsibilities should be clear before comparing the final price.
08 · Customer applications
Relevant industrial project experience
Industrial water-pump application
MAX-MV-060-900
A 6 kV, 900 kW MAX-MV selection is listed for the Yangzi Petrochemical water-pump project. This provides a relevant starting point for discussing a large pump package.
Feedwater pump application
MAX-MV-100-4000
The Lianyungang Petrochemical Industry Base Utilities Island Phase I project includes a 10 kV, 4,000 kW feedwater-pump drive selection.
Discuss a comparable configuration with INOMAX. The motor, equipment scope and operating conditions are assessed separately for each project.
Practical project FAQ
Questions to resolve before ordering
6 questions
Can a 3.3 kV drive be used for a 4.16 kV motor?
Do not select it on motor power alone. The output-voltage capability, transformer, cell configuration, insulation and motor operating point must be matched to the 4.16 kV motor. Send both the supply and motor nameplates so the appropriate configuration can be selected.
What is the difference between a 3.3 kV VFD and a 4.16 kV VFD at 1 MW?
The reference currents and cabinet sizes differ. The 3.3 kV 1,000 kW selection is 219 A with a 4200 × 1300 × 2300 mm base cabinet; the 4.16 kV selection is 170 A with a 3900 × 1200 × 2200 mm base cabinet. Final sizing still depends on the motor and duty.
Can MAX-MV control an existing induction motor?
An existing motor can be considered after its insulation condition, nameplate, cooling at low speed, bearing arrangement and cable circuit are reviewed. The near-sinusoidal multilevel output supports motor applications, but it does not remove the need to check the complete installation.
Can our OEM use the same control signals across different voltage ratings?
A common control-interface specification can be developed for a product family. Agree the I/O list, scaling, alarm definitions, local/remote priority and communication-loss response, then validate the selected drive configuration in the package test.
When should a distributor recommend a soft starter instead?
Use a VFD where continuous speed or process control is required. If the motor only needs controlled starting and then runs at line speed, evaluate a medium-voltage soft starter or an engineered variable-frequency starting scheme against the load and grid requirements.
What do you need for a 3.3 or 4.16 kV quotation?
Start with a motor nameplate, supply voltage, application and required operating speed range. Add the site temperature and altitude, cooling preference, bypass requirement, control protocol and delivery destination. INOMAX can then define the technical scope and commercial offer.
No matching question. Ask our application team.
Technical resources
Catalog, manual & project support
MAX-MV catalog
Ratings, dimensions, features and configuration options.
MAX-MV user manual
Installation, operation, control settings and maintenance.
Project-specific documents
Contact INOMAX for project records, drawings, certificates and test reports matched to your application.
09 · Start the conversation
Let’s define your next MAX-MV project.
Request a Voltage-Matched Selection
Send the motor nameplate, supply voltage and load duty. We will review the current rating, cabinet arrangement and integration options.
Email: info@inomaxtechnology.com