Product overview
AST6200 provides controlled starting and configurable motor protection for three-phase pumps in water-transfer, booster, cooling-water and irrigation systems. It is intended for applications that run at line-frequency motor speed after starting. Select a VFD instead when the process needs continuous flow or pressure regulation through motor speed.
Starting and stopping a pump
| Selection point | Application requirement |
|---|---|
| Starting condition | Identify pump type, static head, valve position, check-valve arrangement and whether the pump starts against pressure. These conditions affect the motor starting duty. |
| Starting mode | Choose voltage ramp, current limit or torque starting during commissioning. Set the initial voltage and ramp to accelerate the actual pump without an unnecessarily long stalled or low-speed period. |
| Soft stop | A configurable 0–60 s soft stop is available. Assess stopping behavior with the hydraulic system; soft stop alone does not guarantee elimination of water hammer. |
| Process interlocks | Coordinate tank level, pressure permissives and external protection with the panel control. Do not assume that every process sensor function is built into the starter. |
Functions and performance
| Function | What it provides |
|---|---|
| Starting modes | Voltage ramp, current-limit and torque starting |
| Starting adjustment | Starting time 1–120 s; initial voltage 30–80%; current-limit setting 50–600% |
| Stopping | Free/coast stop or soft stop; soft-stop time 0–60 s |
| Control | Local keypad, external terminals or communication control, with selectable combinations |
| Display | Removable Chinese/English LCD; operating status, current, voltage and fault information |
| Communication | RS485 Modbus RTU as standard |
| Feedback | One running relay, two programmable relay outputs and 4–20 mA analog output |
| Protection | Configurable overload, overcurrent, voltage, phase, unbalance, underload and thermal functions |
Adjustment ranges are parameter limits, not a guarantee that every motor can start at every setting. Starting duty, load torque and the motor thermal limits govern commissioning. Review the protection response settings: starting overcurrent and underload are set to Ignore by default in the V2612 manual.
How to select the AST6200
- Send motor voltage, rated current, kW, frequency and connection.
- Describe water-transfer, booster, cooling or irrigation duty, including normal start conditions and required stop behavior.
- State starts per hour, longest acceleration, ambient temperature, altitude and panel enclosure.
- Confirm local/remote start, fault feedback, Modbus connection and whether a 4–20 mA signal is needed.
Choose the voltage and current class
| Voltage class | Three-phase supply | Catalog power range | Rated current range |
|---|---|---|---|
| S4 | 380–480 V | 7.5–800 kW | 17–1600 A |
| S2 | 220–240 V | 5.5–400 kW | 23–1400 A |
| S6 | 520–690 V | 7.5–1400 kW | 11–1600 A |
| S11 | 1000–1140 V | 15–800 kW | 10–560 A |
Start from the actual motor nameplate, not only the machine power. Ratings differ by voltage class. Confirm load torque, acceleration, repeated starts and any environmental derating with INOMAX.
What to verify at commissioning
- Record supply voltage and motor current during run-up and steady operation.
- Confirm the pump reaches normal operating speed without extended excessive current.
- Verify start permissives, normal stop, fault response and restart conditions.
- Test the chosen soft-stop time with the hydraulic system and retain the final parameter record.
Installation and operating conditions
| Item | AST6200 specification / selection requirement |
|---|---|
| Motor | Three-phase squirrel-cage asynchronous motor |
| Supply frequency | 30–70 Hz supply frequency; this is not a variable output-frequency range |
| Enclosure and cooling | IP20 unit, forced-air cooling, indoor installation |
| Ambient temperature | −10 to +40 °C; confirm suitability outside the specified range |
| Altitude | Below 2,000 m; derating is required above this altitude |
| Humidity and vibration | Below 95% RH, non-condensing; vibration below 0.5 G |
| Panel design | Keep cooling paths clear; exclude conductive dust, corrosive and explosive gases |
| Duty rating | Select by motor rated current, starting time, load and starts per hour |
Provide upstream isolation and protective devices to the installation design. Do not connect capacitors to the soft starter output. Electrical installation and commissioning must follow the manual and applicable site requirements.
Custom cabinet-type soft starter
INOMAX can supply AST6200 as a custom cabinet-type soft starter for project, system-integrator and OEM requirements. For a pump cabinet, define local or remote start/stop, the pump interlocks and the required stopping behavior.
Specify the required enclosure protection, installation environment, incoming isolation and protection, door controls, cable entry and cooling arrangement. Cabinet dimensions, component selection and supply scope are confirmed for the quoted configuration. The IP20 rating and dimensions in a standard AST6200 datasheet describe the starter unit, not the completed cabinet.

Download a datasheet by voltage and power
Choose the motor supply voltage first, then find its kW reference and compare the starter current with the motor nameplate. Download links show voltage and power as well as the AST6200 model, so the file can be selected without knowing the model code in advance.
- 220–240 V · 5.5–400 kW model datasheets
- 380–480 V · 7.5–800 kW model datasheets
- 520–690 V · 7.5–1400 kW model datasheets
- 1000–1140 V · 15–800 kW model datasheets
These PDFs describe individual starter units. For a custom cabinet, request the agreed cabinet specification and controlled dimensional drawing from info@inomaxtechnology.com.
Frequently asked questions
Can AST6200 regulate pump pressure continuously?
It controls motor starting and stopping. For continuous pressure regulation through motor speed, specify a suitable VFD and pressure-control arrangement.
Does soft stop guarantee no water hammer?
No. The hydraulic layout, valves and operating point must be assessed. Adjust and verify the stopping sequence on the actual system.
Is dry-run protection ready without commissioning?
Do not assume this. Underload protection is configurable and its default response is Ignore in V2612. Verify the protection settings and any required external level or flow protection.
Catalog, manual and selection support
AST6200 English Catalog — V2612 (PDF) · AST6200 User Manual — V2612 (PDF)
Specifications on this page refer to these AST6200 editions. Use the supplied unit nameplate and applicable manual for final installation and commissioning. Download the selected model datasheet using the voltage and power links above. Ask INOMAX for the controlled dimensional drawing and agreed cabinet specification before fabrication.
Soft starter selection for pumps, fans and heavy loads · Browse all AST6200 product options
Specify your AST6200
Send the motor nameplate, application and starts per hour. INOMAX can review the voltage class, current rating, control requirements and cabinet arrangement before quotation.