Product overview
AST6200 is an IP20 online soft-starter unit for OEM equipment panels, motor-control cabinets and distributor projects. Its four voltage classes and multiple frame sizes let panel builders select a unit around the actual motor nameplate and starting duty. The finished cabinet requires its own environmental, protection, cooling and control design.
Cabinet assembly reference

The available AST6200 project photographs show units wired on cabinet mounting plates during workshop assembly. They illustrate an integration format, not a promised enclosure rating, delivery quantity, customer acceptance result or performance measurement. Contact INOMAX to discuss a documented configuration relevant to your project.
Select the power unit before designing the enclosure
Choose the voltage and current class
| Voltage class | Three-phase supply | Catalog power range | Rated current range |
|---|---|---|---|
| S4 | 380–480 V | 7.5–800 kW | 17–1600 A |
| S2 | 220–240 V | 5.5–400 kW | 23–1400 A |
| S6 | 520–690 V | 7.5–1400 kW | 11–1600 A |
| S11 | 1000–1140 V | 15–800 kW | 10–560 A |
Start from the actual motor nameplate, not only the machine power. Ratings differ by voltage class. Confirm load torque, acceleration, repeated starts and any environmental derating with INOMAX.
Identify in-line or inside-delta motor connection at the design stage. Parameter A18 supports these connection selections, but setting the parameter alone is insufficient: the motor lead arrangement, wiring and current selection must follow the applicable manual and reviewed circuit. Do not apply a generic kW or current conversion without confirmation.
Mechanical and thermal planning
| Design item | What the panel builder should confirm |
|---|---|
| Frame size | Use the exact model drawing; the catalog includes several mechanical frames |
| Dimension order | Catalog dimensions are width × depth × height, in mm |
| Packing weight | Catalog gross weight is for one individually packed unit, not the complete cabinet |
| Cooling | Forced-air unit; preserve the specified cooling path and service access |
| Environment | Indoor unit, −10 to +40 °C, below 2,000 m without altitude derating; below 95% RH, non-condensing |
| Enclosure rating | IP20 refers to the starter unit. Agree the rating of a complete cabinet separately |
| Control access | Plan the removable LCD, local/remote selection, service access and operator indication |
Use a controlled dimensional drawing for drilling, busbar layout and cabinet fabrication. Confirm heat dissipation, wiring space and the site environment for the exact assembly. Do not infer a complete IP54 or IP65 cabinet rating from the bare starter unit.
Functions and panel interfaces
- Three starting modes: voltage ramp, current limit and torque starting.
- Free/coast stop or timed soft stop; specify the equipment stopping sequence.
- Standard RS485 Modbus RTU for a suitable PLC/HMI interface.
- One running relay, two programmable relay outputs and 4–20 mA feedback.
- Optional A1/A2 external 220–440 VAC control supply must be specified and confirmed with the order.
- Online/bypass configuration must match the supplied unit, parameter setting and reviewed circuit; upstream isolation and protection remain design requirements.
OEM and distributor enquiry checklist
| Send first | Why it matters |
|---|---|
| Motor nameplate and driven machine | Establish voltage class, rated current and starting load |
| Start duration and starts per hour | Assess repeated-start thermal duty |
| Ambient, altitude and enclosure requirements | Select cooling and any necessary derating |
| Control and feedback requirements | Define local/remote commands, communication, relays and analog signals |
| Supply scope | Distinguish a bare starter, mounting-plate assembly and complete cabinet |
| Destination and project schedule | Confirm documents, support scope, warranty terms and delivery in the quotation |
Custom cabinet-type soft starter
INOMAX can supply AST6200 as a custom cabinet-type soft starter for project, system-integrator and OEM requirements. For OEM panel supply, agree the terminal plan, door controls, wiring identification, enclosure dimensions and documentation scope before manufacture.
Specify the required enclosure protection, installation environment, incoming isolation and protection, door controls, cable entry and cooling arrangement. Cabinet dimensions, component selection and supply scope are confirmed for the quoted configuration. The IP20 rating and dimensions in a standard AST6200 datasheet describe the starter unit, not the completed cabinet.

Download a datasheet by voltage and power
Choose the motor supply voltage first, then find its kW reference and compare the starter current with the motor nameplate. Download links show voltage and power as well as the AST6200 model, so the file can be selected without knowing the model code in advance.
- 220–240 V · 5.5–400 kW model datasheets
- 380–480 V · 7.5–800 kW model datasheets
- 520–690 V · 7.5–1400 kW model datasheets
- 1000–1140 V · 15–800 kW model datasheets
These PDFs describe individual starter units. For a custom cabinet, request the agreed cabinet specification and controlled dimensional drawing from info@inomaxtechnology.com.
Frequently asked questions
Is the complete cabinet automatically IP20?
The published IP20 rating is for the AST6200 unit. A finished cabinet rating depends on the enclosure and assembly design and must be agreed separately.
Can I fabricate from a family photograph?
No. Obtain the exact model dimensional drawing, terminal arrangement and installation requirements before fabrication.
Can the same panel design cover all ten product pages?
These pages describe voltage classes and application or integration needs within AST6200. They are not ten interchangeable hardware models. Select the exact model and review each assembly.
Are customer results or delivery times guaranteed by the assembly photograph?
No. The photograph documents workshop assembly only. Project performance, acceptance criteria, delivery and commercial terms require project-specific confirmation.
Catalog, manual and selection support
AST6200 English Catalog — V2612 (PDF) · AST6200 User Manual — V2612 (PDF)
Specifications on this page refer to these AST6200 editions. Use the supplied unit nameplate and applicable manual for final installation and commissioning. Download the selected model datasheet using the voltage and power links above. Ask INOMAX for the controlled dimensional drawing and agreed cabinet specification before fabrication.
Soft starter selection for pumps, fans and heavy loads · Browse all AST6200 product options
Specify your AST6200
Send the motor nameplate, application and starts per hour. INOMAX can review the voltage class, current rating, control requirements and cabinet arrangement before quotation.
Email: info@inomaxtechnology.com. Confirm warranty coverage, support scope, availability and delivery schedule for the quoted model and destination.