Product overview
Specify an INOMAX AST6200 75 kW soft starter cabinet for a three-phase 380–480 V squirrel-cage motor. The S4 model reference is AST6200-S4-075, 145 A. INOMAX can configure the enclosure, controls and protective-device arrangement to the motor, installation and project requirements.
This page focuses on a 75 kW pump or fan starting package. Review pump stopping behavior or fan acceleration time together with cabinet cooling and process interlocks before choosing the final assembly.
Cabinet configuration is made to order. The photographs show actual AST6200 cabinet assembly examples; they do not establish the motor power, enclosure rating or dimensions of the quoted cabinet.
Cabinet configuration

| Item | Specification or selection requirement |
|---|---|
| Core starter | AST6200-S4-075 online three-phase soft starter, subject to motor-current and duty verification. |
| Enclosure | Specify indoor or other installation conditions, required enclosure protection, cable entry and available mounting space. |
| Protection and isolation | Agree incoming isolation and short-circuit protective devices with the supply and installation design. |
| Operator controls | Define door-mounted start/stop controls, status indication and local/remote operation. |
| Control wiring | Confirm process interlocks, field terminal identification, relay feedback and Modbus RTU requirements. |
| Thermal arrangement | Account for online thyristor operation, ambient temperature, ventilation and repeated starts. |
| Final documentation | Confirm the agreed component list, cabinet dimensions and wiring arrangement before manufacture. |
75 kW starter ratings
| Item | Specification or selection requirement |
|---|---|
| Starter model | AST6200-S4-075 |
| Catalog motor-power reference | 75 kW; select by actual motor rated current and starting duty. |
| Starter rated current | 145 A |
| Supply | Three-phase 380–480 V AC, 30–70 Hz supply frequency. |
| Power circuit | Online thyristor control; the motor remains in the thyristor power circuit during normal running. |
| Starter unit dimensions (H × W × D) | 322 × 173 × 218 mm |
| Starter unit net weight | 7.35 kg |
| Standard starter unit | IP20, forced-air cooling; −10 to +40 °C, indoor installation; below 2,000 m, with derating above 2,000 m. |
Unit dimensions, weight and IP20 protection apply to the individual AST6200 starter. Cabinet dimensions, weight and enclosure protection are defined separately for the ordered assembly.
Functions and performance
| Item | Specification or selection requirement |
|---|---|
| Starting profiles | Voltage ramp, current limit or torque start; select and tune the profile to the motor and load. |
| Starting adjustments | A04 starting time 1–120 s; A03 initial voltage 30–80%; A02 starting current limit 50–600%. |
| Stopping | Coast stop or timed soft stop; A09 soft-stop time 0–60 s. |
| Commands and feedback | Removable Chinese/English LCD, remote terminals, one running relay, two programmable relays and 4–20 mA output. |
| PLC connection | RS485 Modbus RTU; 2400, 4800, 9600 or 19200 bit/s; 8N1. |
| Protection setup | Configurable overload, voltage, phase, current unbalance and temperature responses. Review the V2612 defaults during commissioning: starting overcurrent and underload are set to Ignore. |
Setting ranges are not guaranteed starting capability. The available motor torque, supply capacity, acceleration time and thermal duty determine the usable settings.
75 kW pump and fan applications
For a pump, select the start and stop profile with the hydraulic system in mind. Pipework, valves, static head and pump inertia affect the installed response. Verify pressure transients during commissioning rather than assuming that any soft-stop time will eliminate water hammer.
For a fan or blower, rotor inertia and the required acceleration can extend the start. Check starting torque, supply capacity and motor thermal limits, and include the actual starts per hour in the cabinet review.
For a compressor or conveyor at the same power, supply the loaded or unloaded starting condition and the process sequence; a pump or fan selection cannot simply be transferred to another duty.
How to select a 75 kW soft starter cabinet
- Confirm the three-phase supply voltage and motor connection. Use the S4 table for 380–480 V.
- Compare the motor nameplate current with the 145 A AST6200-S4-075 reference. Review required derating and duty before confirming the size.
- For pumps, describe the hydraulic starting and stopping conditions. For fans, provide inertia or the observed acceleration requirement.
- Confirm starts per hour, ambient temperature, altitude and ventilation. Online thyristor operation must be included in the enclosure thermal assessment.
- Specify process interlocks, local/remote controls, required PLC feedback and the incoming protective-device arrangement.
Frequently asked questions
Can one 75 kW selection cover every pump and fan?
No. Compare motor current, acceleration time, load, supply capacity and starts per hour. AST6200-S4-075 provides the 75 kW / 145 A reference for the 380–480 V class.
Does soft stop guarantee no water hammer?
No. Stopping behavior depends on the pump and hydraulic system. Tune the stop profile and verify the installed pressure response.
Is a bypass contactor included in every cabinet?
Do not assume this. AST6200 is an online soft starter. Any project-specific power-circuit arrangement and component supply must be confirmed in the cabinet specification.
Download the selected model datasheet
AST6200 380–480 V 75 kW Soft Starter Datasheet (PDF)
File model: AST6200-S4-075. The PDF includes unit ratings, starting functions, protection settings, control connections and mechanical data. The download name shows voltage and power so you can identify the correct file without knowing the model code first.
Compare all 380–480 V AST6200 power ratings and datasheets
AST6200 English Catalog V2612 (PDF) · AST6200 User Manual V2612 (PDF)
Project and OEM selection support
Send the motor nameplate, application, starts per hour and cabinet requirements to info@inomaxtechnology.com. INOMAX can review the selected starter and cabinet scope before quotation. Confirm the warranty coverage, commissioning support and delivery schedule for the quoted configuration and destination.
AST6200 for OEM control panels · Soft starter selection for pumps, fans and heavy loads · Browse AST6200 product options
Specify your AST6200
Send the motor nameplate, application and starts per hour. INOMAX can review the voltage class, current rating, control requirements and cabinet arrangement before quotation.