Product overview
AST6200 provides online soft starting for suitable three-phase compressor motors. Compressor type, residual pressure, unloading arrangements and restart frequency are central to selection. An OEM or system integrator should define the starting sequence with the compressor manufacturer before choosing the starter current rating.
Coordinate the compressor starting sequence
| Selection point | Application requirement |
|---|---|
| Compressor type | State the compressor technology and whether the motor starts loaded or unloaded. Do not assume one starting setup suits every compressor. |
| Unloading and pressure | Describe unloading valves, pressure permissives, residual pressure and any minimum restart delay required by the equipment. |
| Starting current | Use voltage-ramp, current-limit or torque starting as appropriate to the machine. A current setting too low to accelerate the compressor can prolong thermal stress. |
| Control integration | Coordinate local/remote commands, running status, fault outputs and external permissives with the compressor controller. |
Functions and performance
| Function | What it provides |
|---|---|
| Starting modes | Voltage ramp, current-limit and torque starting |
| Starting adjustment | Starting time 1–120 s; initial voltage 30–80%; current-limit setting 50–600% |
| Stopping | Free/coast stop or soft stop; soft-stop time 0–60 s |
| Control | Local keypad, external terminals or communication control, with selectable combinations |
| Display | Removable Chinese/English LCD; operating status, current, voltage and fault information |
| Communication | RS485 Modbus RTU as standard |
| Feedback | One running relay, two programmable relay outputs and 4–20 mA analog output |
| Protection | Configurable overload, overcurrent, voltage, phase, unbalance, underload and thermal functions |
Adjustment ranges are parameter limits, not a guarantee that every motor can start at every setting. Starting duty, load torque and the motor thermal limits govern commissioning. Review the protection response settings: starting overcurrent and underload are set to Ignore by default in the V2612 manual.
How to select the AST6200
- Send motor nameplate voltage, power, current and frequency.
- State compressor type and the loaded/unloaded start condition.
- Provide required acceleration, starts per hour, restart interval and controller interfaces.
- Confirm the enclosure, temperature, altitude and cooling arrangement.
Choose the voltage and current class
| Voltage class | Three-phase supply | Catalog power range | Rated current range |
|---|---|---|---|
| S4 | 380–480 V | 7.5–800 kW | 17–1600 A |
| S2 | 220–240 V | 5.5–400 kW | 23–1400 A |
| S6 | 520–690 V | 7.5–1400 kW | 11–1600 A |
| S11 | 1000–1140 V | 15–800 kW | 10–560 A |
Start from the actual motor nameplate, not only the machine power. Ratings differ by voltage class. Confirm load torque, acceleration, repeated starts and any environmental derating with INOMAX.
Protection and commissioning review
Review the inverse-time overload class, starting and running overcurrent settings, voltage limits and fault response with the motor and compressor requirements. The V2612 manual lists selectable responses; starting overcurrent is set to Ignore by default. Verify the agreed start sequence, motor current, normal stop, fault handling and restart permissives before handover.
Installation and operating conditions
| Item | AST6200 specification / selection requirement |
|---|---|
| Motor | Three-phase squirrel-cage asynchronous motor |
| Supply frequency | 30–70 Hz supply frequency; this is not a variable output-frequency range |
| Enclosure and cooling | IP20 unit, forced-air cooling, indoor installation |
| Ambient temperature | −10 to +40 °C; confirm suitability outside the specified range |
| Altitude | Below 2,000 m; derating is required above this altitude |
| Humidity and vibration | Below 95% RH, non-condensing; vibration below 0.5 G |
| Panel design | Keep cooling paths clear; exclude conductive dust, corrosive and explosive gases |
| Duty rating | Select by motor rated current, starting time, load and starts per hour |
Provide upstream isolation and protective devices to the installation design. Do not connect capacitors to the soft starter output. Electrical installation and commissioning must follow the manual and applicable site requirements.
Custom cabinet-type soft starter
INOMAX can supply AST6200 as a custom cabinet-type soft starter for project, system-integrator and OEM requirements. For a compressor cabinet, confirm the unloading sequence, pressure-control interface and restart requirements.
Specify the required enclosure protection, installation environment, incoming isolation and protection, door controls, cable entry and cooling arrangement. Cabinet dimensions, component selection and supply scope are confirmed for the quoted configuration. The IP20 rating and dimensions in a standard AST6200 datasheet describe the starter unit, not the completed cabinet.

Download a datasheet by voltage and power
Choose the motor supply voltage first, then find its kW reference and compare the starter current with the motor nameplate. Download links show voltage and power as well as the AST6200 model, so the file can be selected without knowing the model code in advance.
- 220–240 V · 5.5–400 kW model datasheets
- 380–480 V · 7.5–800 kW model datasheets
- 520–690 V · 7.5–1400 kW model datasheets
- 1000–1140 V · 15–800 kW model datasheets
These PDFs describe individual starter units. For a custom cabinet, request the agreed cabinet specification and controlled dimensional drawing from info@inomaxtechnology.com.
Frequently asked questions
Will soft starting replace the unloading system?
No. Keep the compressor manufacturer’s unloading and restart requirements in the control design.
Can the same model be selected only by compressor kW?
No. Confirm motor rated current and the actual starting duty, including loaded starts and repeated starts.
Does AST6200 provide variable-speed compressor control?
It is a motor soft starter. Continuous speed control requires a suitable VFD and a compressor system designed for that operating mode.
Catalog, manual and selection support
AST6200 English Catalog — V2612 (PDF) · AST6200 User Manual — V2612 (PDF)
Specifications on this page refer to these AST6200 editions. Use the supplied unit nameplate and applicable manual for final installation and commissioning. Download the selected model datasheet using the voltage and power links above. Ask INOMAX for the controlled dimensional drawing and agreed cabinet specification before fabrication.
Soft starter selection for pumps, fans and heavy loads · Browse all AST6200 product options
Specify your AST6200
Send the motor nameplate, application and starts per hour. INOMAX can review the voltage class, current rating, control requirements and cabinet arrangement before quotation.
Email: info@inomaxtechnology.com. Confirm warranty coverage, support scope, availability and delivery schedule for the quoted model and destination.