Product overview
AST6200 can be specified for suitable three-phase conveyor and material-handling motors that need controlled starting at a fixed running speed. The selection must account for loaded starts, mechanical resistance, starting torque and the conveyor control sequence. This page is for motor-starter selection rather than a claim of a completed conveyor project.
Match the starter to the conveyor duty
| Selection point | Application requirement |
|---|---|
| Loaded or empty start | Identify the heaviest expected starting condition. An unloaded test alone does not establish suitability for restarting a loaded conveyor. |
| Acceleration | Voltage-ramp, current-limit and torque-starting modes are available. Commission the mode and settings against the required acceleration and mechanical load. |
| Sequencing | Coordinate upstream and downstream equipment permissives, running indication and fault responses in the machine control. |
| Stopping and safety | Free stop and timed soft stop are supported. Do not treat soft stop as a safety-rated stop or as a substitute for the machine safety system. |
Functions and performance
| Function | What it provides |
|---|---|
| Starting modes | Voltage ramp, current-limit and torque starting |
| Starting adjustment | Starting time 1–120 s; initial voltage 30–80%; current-limit setting 50–600% |
| Stopping | Free/coast stop or soft stop; soft-stop time 0–60 s |
| Control | Local keypad, external terminals or communication control, with selectable combinations |
| Display | Removable Chinese/English LCD; operating status, current, voltage and fault information |
| Communication | RS485 Modbus RTU as standard |
| Feedback | One running relay, two programmable relay outputs and 4–20 mA analog output |
| Protection | Configurable overload, overcurrent, voltage, phase, unbalance, underload and thermal functions |
Adjustment ranges are parameter limits, not a guarantee that every motor can start at every setting. Starting duty, load torque and the motor thermal limits govern commissioning. Review the protection response settings: starting overcurrent and underload are set to Ignore by default in the V2612 manual.
How to select the AST6200
- Provide motor voltage, kW, current, frequency and connection.
- Describe conveyor type, loading, gradient where applicable, driven inertia and breakaway conditions.
- Specify acceleration time, starts per hour and any required sequence between machines.
- List PLC, relay, analog-feedback and external-interlock needs.
Choose the voltage and current class
| Voltage class | Three-phase supply | Catalog power range | Rated current range |
|---|---|---|---|
| S4 | 380–480 V | 7.5–800 kW | 17–1600 A |
| S2 | 220–240 V | 5.5–400 kW | 23–1400 A |
| S6 | 520–690 V | 7.5–1400 kW | 11–1600 A |
| S11 | 1000–1140 V | 15–800 kW | 10–560 A |
Start from the actual motor nameplate, not only the machine power. Ratings differ by voltage class. Confirm load torque, acceleration, repeated starts and any environmental derating with INOMAX.
Commissioning and acceptance points
- Test the agreed empty and loaded starting conditions.
- Record run-up time and motor current and compare them with the approved duty.
- Verify conveyor permissives, running status, faults and the intended restart behavior.
- Review motor overload settings and the external protection coordination before handover.
Installation and operating conditions
| Item | AST6200 specification / selection requirement |
|---|---|
| Motor | Three-phase squirrel-cage asynchronous motor |
| Supply frequency | 30–70 Hz supply frequency; this is not a variable output-frequency range |
| Enclosure and cooling | IP20 unit, forced-air cooling, indoor installation |
| Ambient temperature | −10 to +40 °C; confirm suitability outside the specified range |
| Altitude | Below 2,000 m; derating is required above this altitude |
| Humidity and vibration | Below 95% RH, non-condensing; vibration below 0.5 G |
| Panel design | Keep cooling paths clear; exclude conductive dust, corrosive and explosive gases |
| Duty rating | Select by motor rated current, starting time, load and starts per hour |
Provide upstream isolation and protective devices to the installation design. Do not connect capacitors to the soft starter output. Electrical installation and commissioning must follow the manual and applicable site requirements.
Custom cabinet-type soft starter
INOMAX can supply AST6200 as a custom cabinet-type soft starter for project, system-integrator and OEM requirements. For a conveyor cabinet, describe whether starts are loaded, the process interlocks and the permitted restart sequence.
Specify the required enclosure protection, installation environment, incoming isolation and protection, door controls, cable entry and cooling arrangement. Cabinet dimensions, component selection and supply scope are confirmed for the quoted configuration. The IP20 rating and dimensions in a standard AST6200 datasheet describe the starter unit, not the completed cabinet.

Download a datasheet by voltage and power
Choose the motor supply voltage first, then find its kW reference and compare the starter current with the motor nameplate. Download links show voltage and power as well as the AST6200 model, so the file can be selected without knowing the model code in advance.
- 220–240 V · 5.5–400 kW model datasheets
- 380–480 V · 7.5–800 kW model datasheets
- 520–690 V · 7.5–1400 kW model datasheets
- 1000–1140 V · 15–800 kW model datasheets
These PDFs describe individual starter units. For a custom cabinet, request the agreed cabinet specification and controlled dimensional drawing from info@inomaxtechnology.com.
Frequently asked questions
Can torque starting guarantee breakaway under any load?
No. The starting mode must be matched to the motor and mechanical load. Submit the worst-case starting duty for selection.
Is it a positioning or variable-speed conveyor drive?
No. Specify a suitable drive when the conveyor requires continuous speed control, synchronization or positioning.
Does the starter provide the complete machine safety function?
The machine control and safety design remain separate requirements. Do not infer a safety rating from standard start/stop inputs or protection relays.
Catalog, manual and selection support
AST6200 English Catalog — V2612 (PDF) · AST6200 User Manual — V2612 (PDF)
Specifications on this page refer to these AST6200 editions. Use the supplied unit nameplate and applicable manual for final installation and commissioning. Download the selected model datasheet using the voltage and power links above. Ask INOMAX for the controlled dimensional drawing and agreed cabinet specification before fabrication.
Soft starter selection for pumps, fans and heavy loads · Browse all AST6200 product options
Specify your AST6200
Send the motor nameplate, application and starts per hour. INOMAX can review the voltage class, current rating, control requirements and cabinet arrangement before quotation.