← MAX-MV series overview · Explore all 10 selection guides
01 · Product overview
Cooling is part of the drive system.
MAX-MV offers forced-air and water-cooled configurations for medium-voltage motor control. The choice changes how heat leaves the power stage and transformer, which auxiliary equipment is needed and how the installation is maintained. It should be made alongside the voltage, power, enclosure and available site utilities.
In the forced-air arrangement, incoming air passes through power-unit heat sinks and the transformer air path, with top-mounted fans exhausting heated air. A water-cooled project requires a defined cooling circuit and heat-rejection arrangement. The final cabinet construction and residual heat released into the room depend on the selected design.
02 · Rating and cabinet selection
Power, voltage and current selection
Match the motor nameplate current, overload duty and site derating before confirming a model. The filters below help you compare the listed selections; final cabinet and option details are agreed for the project.
7 reference selections
No matching selection in this table. Send your motor data for engineering review.
Dimensions exclude top fans, bypass additions and service clearances. At 6.6 kV from 2,800 kW and 11 kV from 4,500 kW, add an 800 mm current-limiting cabinet with matching depth and height. Use the approved project drawing for the complete installation.
Cooling comparison
Air cooling or water cooling?
| Decision | Air-cooled package | Water-cooled package |
|---|---|---|
| Heat rejection | Ventilation, exhaust duct or room HVAC | Defined liquid circuit and external heat rejection, plus residual room losses |
| Site information | Inlet air temperature, airflow, dust and available exhaust route | Coolant quality, inlet temperature, flow, pressure and heat-exchanger arrangement |
| Auxiliary scope | Fans, filtration and any ductwork/HVAC | Pumps, heat exchanger, valves, instrumentation and circuit protection as agreed |
| Maintenance planning | Fan and filter access; clear air passages | Water/coolant condition and circuit maintenance; leak/flow supervision |
03 · Application fit
Application requirements that shape the package
Ventilated electrical rooms
Air cooling can suit installations with adequate clean airflow and planned exhaust or HVAC capacity.
Restricted heat rejection
Water cooling can be evaluated where a suitable cooling-water or closed-loop heat-rejection system is available and room heat removal is constrained.
Dusty, humid or demanding sites
Coordinate enclosure protection, filtration, condensation control and cooling. An enclosure rating alone does not establish suitability for corrosive or explosive conditions.
04 · Integration and options
Functions, accessories and engineering decisions
Define air inlet and exhaust conditions
Provide the maximum air temperature at the actual cabinet inlet. Avoid recirculating hot exhaust into the inlet or blocking the top fan discharge. Ducting, pressure loss, filters and room airflow must be coordinated with the selected fan arrangement.
Specify the complete water loop
Agree coolant quality and composition, inlet temperature, flow, pressure, permitted pressure drop and heat-exchanger duty. Identify who supplies pumps, valves, monitoring and the external heat rejection. Exact values follow the chosen drive configuration.
Prevent condensation and unintended exposure
Cooling-water temperature and room humidity must be considered together. Define the startup and shutdown sequence, temperature supervision and response to cooling loss. Standard indoor cabinets require protection from water ingress, corrosive gas and conductive contamination.
Include maintenance and cooling-failure response
The platform supports fan supervision, overtemperature protection and configured fan redundancy. A water-cooled package needs an agreed response to loss of flow or heat rejection. Plan accessible filters, fans, heat exchangers and replaceable components for the local service team.
Define the equipment scope
| Configuration item | What to agree |
|---|---|
| Motor control and feedback | Motor technology, control mode and encoder interface where required |
| Bypass / isolation | Manual or automatic line bypass, isolation and switching interlocks; selected for the process |
| Control integration | Standard Modbus RTU / I/O; optional PROFIBUS DP or exact TCP/IP arrangement |
| Continuity options | Cell-bypass strategy, controller redundancy or standby drive as project-selected |
| Service package | Spare cells, fans, boards, commissioning and training scope |
05 · Electrical performance
Performance for a defined operating duty
| Performance item | Selection basis |
|---|---|
| Motor-control modes | V/F; V/F with feedback; sensorless vector; closed-loop vector |
| Overload capability | 120% for 120 s; 150% for 5 s, checked against selected configuration and duty |
| Frequency resolution | 0.01 Hz; resolution is distinct from motor-speed accuracy |
| Acceleration / deceleration | 0.1–3,600 s; set within motor and process limits |
| Inverter efficiency | 98.5%; excludes the phase-shifting transformer |
| Power factor | ≥0.96 at the specified operating conditions |
| Harmonic performance | THD ≤4% for 3–4.16 kV; ≤2% for 6–13.8 kV. Confirm measurement point, loading and network conditions. |
Confirm performance at the required motor duty, supply conditions and cooling arrangement. For regenerative or braking loads, specify the operating cycle so a suitable two- or four-quadrant power stage can be selected.
06 · Technical data
Installation, environment and maintenance
| Item | Requirement / configuration |
|---|---|
| Operating temperature | −10 to +40°C; higher temperature requires an approved cooling and derating plan |
| Humidity | 20–90% RH, non-condensing, as the installation basis; confirm higher-humidity configurations |
| Altitude | Provide the site elevation; above 1,000 m, review insulation, cooling and derating for the selected configuration |
| Storage | −40 to +70°C; dry, protected storage without condensation or outdoor exposure |
| Cooling and enclosure | Forced air or water cooling; IP31 standard, IP42 optional, custom IP54 |
| Control supply | 220 V AC, 3 kVA, 50/60 Hz; optional DC supply by project arrangement |
| Control interfaces | 3 analog inputs / 4 analog outputs; 8 digital inputs / 5 digital outputs; RS485 / Modbus RTU standard |
| Installation | Indoor electrical room; no explosive/corrosive gases, conductive dust or oil mist; keep cooling and service access clear |
Plan safe service access, delivery openings, foundation loading and separate power/control cable routes. Inspection intervals and replacement work follow the installed equipment manual and the site maintenance plan.
07 · Supplier and configuration comparison
Compare complete proposals on the same basis
| Comparison point | What to check |
|---|---|
| Heat path | Air: room/exhaust airflow. Water: liquid circuit plus residual room losses. |
| Site services | Air: ventilation/HVAC and clear airflow. Water: specified coolant, pumping and external heat rejection. |
| Maintenance | Air: fans, filters and ducts. Water: circuit condition, pump/heat-exchanger service and leakage checks. |
| Selection basis | Compare complete auxiliary equipment, operating costs, available space and service capability. |
Ask each supplier to identify inclusions, exclusions and deviations. The selected rating, options, installation work, acceptance test and service responsibilities should be clear before comparing the final price.
08 · Customer applications
Relevant industrial project experience
Jiangsu Jurong Chemical
10 kV · 4,000 kW
MAX-MV-100-4000 was applied to rich-gas compressor variable-speed control in 2015. The application illustrates coordination of a large motor drive with an industrial process.

Discuss a comparable configuration with INOMAX. The motor, equipment scope and operating conditions are assessed separately for each project.
Practical project FAQ
Questions to resolve before ordering
6 questions
Is water cooling always better for a high-power VFD?
No. The preferred arrangement depends on available cooling utilities, room ventilation, ambient conditions, layout and maintenance resources. Compare the complete installed cooling system and its lifecycle cost for the actual drive rating.
Does a water-cooled drive eliminate the need for electrical-room cooling?
Not automatically. Control equipment, auxiliaries and parts of the power package may still release heat into the room. Obtain the project heat-loss schedule with the split between liquid cooling and ambient air before sizing room ventilation or HVAC.
Can an air-cooled MAX-MV be installed in a dusty mining plant?
Assess the electrical-room environment and required protection. Filtration, room pressurization, cooling arrangements or a customized enclosure may be needed. Standard indoor equipment should not be exposed to conductive dust, corrosive gases or oil mist.
Can you supply IP54 medium-voltage drives?
A custom IP54 arrangement can be engineered. Specify the rating, ambient conditions, cooling method, cable entry and service access so the enclosure and thermal design are coordinated. Confirm the final dimensions and scope in the project drawing.
What cooling-water flow and temperature are required?
There is no single value for every MAX-MV water-cooled system. Flow, inlet temperature, pressure, coolant quality and heat rejection must be specified for the selected rating and circuit. Provide the site cooling-water data with the enquiry.
Can we convert an existing air-cooled installation to water cooling?
Treat this as a system redesign. The power modules, cabinet, cooling circuit, protection and site auxiliaries need to be assessed together. Do not assume that adding an external water connection converts an existing air-cooled cabinet.
No matching question. Ask our application team.
Technical resources
Catalog, manual & project support
MAX-MV catalog
Ratings, dimensions, features and configuration options.
MAX-MV user manual
Installation, operation, control settings and maintenance.
Project-specific documents
Contact INOMAX for project records, drawings, certificates and test reports matched to your application.
09 · Start the conversation
Let’s define your next MAX-MV project.
Compare Cooling Options for Your Site
Share the motor rating, maximum room temperature, available cooling water, enclosure requirement and electrical-room layout.
Email: info@inomaxtechnology.com
Build your local MAX-MV business
Discuss the industries you serve, application-engineering support, training, commissioning and spare-parts planning. Commercial and service arrangements are defined for your market and projects.