POWER GENERATION · ENGINEERING CASE

3 MW-Class Steam Turbine Power Conversion Solution

High-speed PM generator · Three-level conversion · INOMAX ACS890

A liquid-cooled converter proposal connecting a high-speed permanent-magnet generator to a 690 V, 50 Hz grid, with coordinated control and fault-energy management.

Explore the solution

ACS890 seriesThree-level topologyLiquid-cooled modules
Reference INOMAX cabinet assembly · Engineering proposal
3 MWGenerator nameplate rating
8,000 rpmRated generator speed
690 VSpecified grid connection
≤2.5 MWProposed generating duty

01 / PROJECT OVERVIEW

High-speed generation.
Controlled grid connection.

A high-speed permanent-magnet generator requires more than a conventional motor-drive selection.

The application calls for active generator speed control and conversion of generated electrical energy into a fixed-voltage, fixed-frequency grid supply. INOMAX’s ACS890 proposal coordinates the generator-side converter, grid-side AFE, liquid cooling and braking branch.

The generator is rated at 3,000 kW and 8,000 rpm. The proposal separately defines the generating duty as up to 2.5 MW. This engineering case explains the selection and integration approach for that duty.

Three-level main circuit · Grid side and generator side
8,000 rpmGenerator operating speed+10%Overspeed requirement in the proposal

02 / ENGINEERING REQUIREMENTS

Protect the generator.
Control the energy.

  1. High-speed machine protectionConsider back EMF, overspeed voltage, insulation coordination and switching stress.
  2. Grid-compatible conversionDeliver the specified 690 V, 50 Hz connection and assess power quality for the actual network.
  3. Controlled stopping under faultsCoordinate steam-valve closure, generator control and temporary energy dissipation.
  4. Module and thermal integrationEngineer parallel power modules, current sharing and a closed liquid-cooling circuit.

03 / INOMAX SOLUTION

One coordinated conversion system.
From generator to grid.

The proposed ACS890 architecture separates application control from the power units while coordinating the complete energy path.

01

Three-level conversion

Selected to address harmonics, dv/dt and voltage stress in the high-speed PM application.

02

Parallel power modules

Four 900 kW AFE modules provide 3.6 MW of installed module capacity before application-specific limits.

03

Fault-energy management

A separate braking branch and UPS-backed controls support the proposed stopping strategy.

04

Liquid-cooling integration

Parallel coolant paths and thermal supervision are considered together with cabinet design.

CONVERTER CABINET ARRANGEMENTReference envelope · 4,500 × 1,000 × 2,260 mm
CONTROL PLATFORM ARCHITECTUREApplication control · Power-unit execution · Diagnostics

Conceptual cabinet and platform views from the engineering proposal. The control-platform illustration is not an equipment quantity schedule.

Explore the generation and fault-energy pathsGenerator control, AFE regulation and the braking branch

GENERATIONHigh-speed
PM generator

→

MACHINE SIDESpeed-controlled
converter

→

POWER LINKDC bus
+ braking branch

→

GRID SIDEAFE
690 V / 50 Hz

During generation

The generator-side converter controls speed; the AFE maintains DC-link voltage. Steam flow determines generated power after the startup torque limit is released.

During a grid fault

The proposed sequence closes the steam valve and directs surplus energy to the braking resistor while generator control remains available. UPS-backed control supports the blackout stop sequence.

04 / TECHNICAL DATA

Generator data leads the selection.

Selected application and equipment data from the ACS890 engineering proposal.

Generator and operating basis

Parameter Project design basis
Machine type High-speed permanent magnet
Rated power / current 3,000 kW / 2,828 A
Voltage / phases ≤690 V / 3-phase
Rated speed / frequency 8,000 rpm / 266.7 Hz
Rated efficiency / duty ≥96.4% / S1 continuous
Control requirement Sensorless open-loop operation
Defined generating duty Up to 2.5 MW

Conversion and thermal design

Parameter Proposal value
Grid connection 690 V / 50 Hz
AFE installed module capacity 4 × 900 kW = 3.6 MW
Peak braking module capacity 2 × 1,800 kW = 3.6 MW
Pure-water cabinet flow ≥410 L/min
80:20 water / glycol flow ≥440 L/min
Cooling inlet temperature 28–38 °C
Operating pressure 2–6 bar

Efficiency is the generator nameplate specification. Installed module capacity and peak braking capacity are not continuous plant-output ratings. Cooling-unit selection is subject to the final heat-duty and hydraulic checks.

Main equipment proposed for the system

Equipment INOMAX model Rating / role Qty.
Liquid-cooled AFE ACS890-T821-0761-7 900 kW / 690 V 4
Generator-side inverter ACS890-T83-1123-9 1,400 kW at 900 V / 1,100 kW at 690 V 4
Braking module ACS890-T834-1200-15 1,800 kW / 1,500 V DC 2
AC LC filter SLC-270U-600-7-LA Grid-side filtering 4
Balancing reactor ACL-10U-1000 Parallel current sharing 4
Main control unit CU200 Separated control and power 2

The equipment schedule is part of an engineering proposal. Final current ratings, cooling duty and stopping requirements are verified during detailed engineering.

05 / ENGINEERING VALUE

A system response to specific operating demands.

Selection goes beyond total kilowatts to address machine behaviour, grid conditions and stopping energy.

01

Generator-specific design

High speed, PM back EMF and the overspeed requirement shape voltage margin and converter selection.

02

Coordinated fault response

The proposed control sequence links steam-valve closure, generator deceleration, the braking branch and UPS-backed controls.

03

Integrated thermal design

Liquid-cooled modules, parallel circuits and cabinet requirements define the thermal interface for the complete system.

Proposed generation sequence

  1. 01 · PrechargePrepare the grid-side circuit and enter standby.
  2. 02 · Establish DC linkAFE regulation and generator torque limitation.
  3. 03 · Admit steamOpen the inlet valve and approach the target speed.
  4. 04 · GenerateMachine-side speed control and grid-side DC regulation.

06 / ENGINEERING TOOLS & RECORDS

Detailed interfaces support practical integration.

Reference equipment and technical illustrations accompany the engineering proposal.

PARALLEL LIQUID-COOLING CIRCUITReference circuit · Diagram temperatures are illustrative
COMMISSIONING & DIAGNOSTICSReference interface · 16-channel waveform recording
PLC / DCS integration

PROFINET, EtherCAT, EtherNet/IP, Modbus TCP and CANopen options described in the platform proposal.

Local & PC operation

Parameter access, fault review and waveform tools support commissioning and troubleshooting.

Engineering status

This is a proposal-stage case. Reference images and software waveforms are not site acceptance results.

FOR YOUR NEXT PROJECT

Building or modernizing a turbine generation package?

For steam turbine OEMs, generator manufacturers, power-system integrators and industrial plant engineering teams.

Turbine & generator OEMs

Match a converter to the generator’s speed, current, voltage and overspeed envelope. Define control responsibility between the turbine and electrical package.

EPCs & system integrators

Coordinate grid connection, plant PLC or DCS interfaces, cooling and fault handling. Establish the converter supplier’s scope and the site acceptance plan.

Plant owners & retrofit teams

Evaluate a replacement converter or a new waste-heat generation package using the existing generator and plant data. Compare engineering scope, protection and lifecycle support.

This reference shows the ACS890 engineering approach through a generator schedule, converter selection, cabinet arrangement and protection concept. It is a proposal-stage reference; operating results are not claimed.

Explore application and selection questions ↓

07 / YOUR APPLICATION QUESTIONS

Selecting a generator
converter partner?

Generator compatibility, converter replacement, grid connection and protection for your project.

Start with your application. Use these answers to identify what can carry over, what needs engineering and what to confirm before ordering.

Discuss your requirements ↗

01Converter & generator compatibility

Can INOMAX replace an ABB, Siemens or other generator converter?

INOMAX can evaluate an alternative converter package for an existing turbine-generator system. The replacement review covers generator type, speed and voltage envelope, continuous current, grid-side functions, control ownership and fault protection. Provide the original converter specifications, generator data and plant diagrams. Existing equipment can be retained where compatible, but matching a brand’s headline kW rating does not establish an interchangeable converter or control system.

Can INOMAX match a different high-speed permanent-magnet generator?

Yes, a project-specific selection can be evaluated for another high-speed PM generator. Required data include pole count, rated and maximum speed, electrical frequency, current, back-EMF curve, inductance, insulation limits and feedback requirements. A generator with the same power can impose very different voltage and switching requirements. The 8,000 rpm machine in this proposal provides a design example, not a universal speed or frequency limit.

Can a converter be selected for 1 MW, 2 MW, 3 MW or a larger generation project?

INOMAX can review different power levels using an application-specific converter and module arrangement. Continuous electrical output, generator current, overload duty, voltage, cooling and grid-side capacity determine the selection. Installed module capacity must not be treated as guaranteed plant output. This reference uses a 3 MW-nameplate generator with a separately defined generating duty of up to 2.5 MW; a different duty requires a new electrical and thermal check.

Can the system connect to a 400 V or 690 V, 50 Hz or 60 Hz grid?

Different grid voltages and frequencies can be assessed during system design. Generator-side voltage and grid-side voltage must be considered separately, together with converter ratings, DC-link limits, filters, protection and any transformer. This proposal specifies 690 V, 50 Hz. A 400 V or 60 Hz requirement should be included at enquiry stage so the grid interface is engineered for that network rather than assumed compatible with the reference design.

Can this approach be used for waste-heat recovery, CHP or other turbine generation?

It is relevant to projects that need controlled conversion between a variable-frequency generator and an electrical supply, including suitable steam-based waste-heat recovery and combined heat and power (CHP) applications. Feasibility depends on the generator, turbine operating range, required controls and grid connection. Other prime movers or generator technologies require their own review. This case demonstrates an engineering approach; it does not establish a completed installation in every adjacent application.

02Topology, grid operation & protection

When should I choose a three-level converter rather than a conventional drive?

A three-level topology is worth evaluating when machine voltage, switching stress, harmonics or a high-speed generator’s insulation requirements make waveform quality especially important. The choice must consider motor-side dv/dt, electrical frequency, cooling, filters and total system complexity. INOMAX selected three-level conversion for this PM-generator proposal. Another machine may need a different topology; the selection should follow generator and grid requirements rather than power rating alone.

Can the generator converter operate off-grid or provide black-start capability?

Grid-connected, islanded and black-start operation require different control and protection functions. This engineering case addresses grid-connected generation and should not be treated as proof of grid-forming or black-start capability. If island operation is required, specify how voltage and frequency will be established, how loads are shared, the available starting energy and the transfer sequence. INOMAX can review the additional scope with the turbine and plant-control suppliers.

How is a high-speed PM generator protected during a grid fault or emergency stop?

The protection concept must address continuing turbine input, rotor energy, generator back EMF and the loss of a grid export path. In the proposed approach, steam-valve closure, controlled deceleration and a braking branch are coordinated, with UPS-backed controls for the intended stop sequence. Braking energy and thermal duty need calculation; a peak braking-module rating alone does not establish stopping capability. Independent turbine protection and mechanical overspeed protection remain part of the overall system design.

Can INOMAX use the existing plant cooling system or offer an air-cooled alternative?

The existing cooling system can be assessed against converter heat loss, coolant quality, temperature, flow, pressure and materials compatibility. A liquid-cooled arrangement is used in this proposal. If air cooling is preferred, the power-module selection, ventilation demand, ambient conditions and cabinet space must be reviewed as a different design. Cooling-unit supply and the boundary between internal and plant-side circuits should be stated explicitly in the quotation.

03Plant integration & procurement

Can the converter integrate with our turbine controller, PLC or DCS?

The control architecture can be developed around agreed speed, power and torque commands, status feedback, trips and interlocks. Define which controller owns each operating mode and how the system behaves after a communication failure. The platform proposal describes PROFINET, EtherCAT, EtherNet/IP, Modbus TCP and CANopen options; the selected hardware and protocol must be confirmed for the actual project. Interface mapping and acceptance tests belong in the engineering scope.

What grid-code, harmonic and safety compliance can INOMAX provide?

Compliance must be defined against the installation country, utility requirements and selected equipment. Request the applicable product certificates and test reports, and agree the site-specific harmonic, protection, EMC and grid-connection requirements before ordering. An AFE or low-harmonic topology alone does not establish utility approval. The proposal should allocate responsibility for network studies, protection settings, required tests and final acceptance, rather than assume that a reference design is pre-approved for every grid.

What should an OEM or EPC include in a converter enquiry and quotation comparison?

Provide the generator data and back-EMF curve, turbine operating and trip requirements, grid information, load profile, cooling conditions, control interfaces and target schedule. Compare converters on continuous duty, fault-energy handling, filters, cabinet and cooling scope, engineering documentation, FAT, commissioning responsibilities, spare parts and warranty. INOMAX can discuss a defined converter package within the wider turbine project; turbine, generator, civil works and site services should each have an explicit scope owner.

CUSTOMER PRIVACY & CONFIDENTIALITY

More detail. Shared responsibly.

To respect our customers’ privacy and confidentiality commitments, selected customer identities, original drawings and project-specific information are not published. INOMAX works with customers under confidentiality agreements where applicable.

If you are evaluating a similar application, contact the INOMAX sales team. We welcome technical discussions and can share further relevant information within the limits of our confidentiality obligations.

LET’S DISCUSS YOUR APPLICATION

Specify the converter
your generator needs.

Share the generator data, speed and voltage range, grid requirements and project schedule. We’ll discuss the electrical design, protection concept and converter supply scope.

INOMAX · INDUSTRIAL DRIVE SOLUTIONS

Technical project enquiries

Project-specific drive and power conversion systems

info@inomaxtechnology.comwww.inomaxtechnology.com